5.17 Priority list

Example
A6V10733786_en_c
Different functions require priorities over other functions so that logical/critical
operation can be guaranteed.
Safety functions
1
Off by smoke detector, emergency, supply air temperature or extract air
temperature
2
Off by fire damper closed
3
Purge or smoke extract by smoke detector
Protection functions
4
Off by water heating coil frost
5
A-Alarms for plant protection
6
ERC deicing function
Switch or push button operations
7
Rapid ventilation mode (Configured BI, POS8)
8
Comfort mode (Conf. BI), Fireplace (Conf. BI), Off mode (Conf. BI), Eco
mode (Conf. BI)
9
Kitchen ventilator (Conf. BI)
10 Maintenance function
User operation
11 Temporary fireplace (POS8)
12 Present / Away button
13 Manual operation
Automatic function
14 Scheduler operation mode
Application functionalities
Priority list
129 | 170