Campbell Measurement and Control Module CR10 Operator's Manual page 165

Ds 70;
Hide thumbs Also See for Measurement and Control Module CR10:
Table of Contents

Advertisement

SECTION 11. OUTPUT PROCESSING INSTRUCTIONS
*** 71 AVERAGE ***
FUNCTION
This instruction stores the average value over
the given output interval for each input location
specified.
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
4
Outputs Generated:
*** 72 TOTALIZE ***
FUNCTION
This instruction stores totalized value over the
given output interval for each input location
specified.
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
4
Outputs Generated:
*** 73 MAXIMIZE ***
FUNCTION
This instruction stores the MAXIMUM value taken
(for each input location specified) over a given
output interval. An internal FLAG is set whenever a
new maximum value is seen. This FLAG may be
tested by Instruction 79. Time of occurrence
maximum value(s) is OPTIONAL output
information, which is formatted and activated by
entering one of the following CODES for Param. 2.
Code
Options
00
Output value ONLY
01
Output value with SECONDS
10
Output value with HOUR-MINUTE
11
Output value with HR-MIN,SEC
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
2
03:
4
11-4
DESCRIPTION
Repetitions
Starting input location no.
1 for each input location
DESCRIPTION
Repetitions
Starting input location no.
1 for each input location
DESCRIPTION
Repetitions
Time of maximum
(optional)
Starting input location no.
Outputs Generated:
location (plus 1 or 2 with time of max. option)
*** 74 MINIMIZE ***
FUNCTION
Operating in the same manner as Program 73,
this instruction is used for storing the MINIMUM
value (for each input location specified) over a
given output interval.
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
2
03:
4
Outputs Generated:
location (plus 1 or 2 with time of min. option)
*** 75 STANDARD AND WEIGHTED ***
VALUE HISTOGRAM
FUNCTION
Processes input data as either a standard
histogram (frequency distribution) or a weighted
value histogram.
The standard histogram outputs the fraction of
the Output Interval that the value in a specified
input location (defined as the bin select value)
is within a particular sub-range of the total
specified range. A counter in the bin
associated with each sub-range is incremented
whenever the value falls within that sub-range.
The value which is output to Final Storage for
each bin is computed by dividing the
accumulated total in each bin by the total
number of scans. This form of output is also
referred to as a frequency distribution.
The weighted value histogram uses data from 2
input locations. One location contains the bin
select value; the other contains the weighted
value. Each time the instruction is executed,
the weighted value is added to a bin. The sub-
range that the bin select value is in determines
the bin to which the weighted value is added.
When the Output Flag is set, the value
accumulated in each bin is divided by the
TOTAL number of input scans to obtain the
values that are output to Final Storage. These
1 for each input
DESCRIPTION
Repetitions
Time of minimum
(optional)
Starting input location
no.
1 for each input

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ds 70

Table of Contents

Save PDF