SECTION 9. INPUT/OUTPUT INSTRUCTIONS
Range Code
Slow
Fast
2.72ms
250µs
Integ.
Integ.
1
11
2
12
3
13
4
14
5
15
* Differential measurement; resolution for single-ended measurement is twice value shown.
NOTE: When a voltage input exceeds the range programmed, the value which is stored is set to
the maximum negative number and displayed as -99999 in high resolution or -6999 in low
resolution.
*** 1 SINGLE-ENDED VOLTS ***
FUNCTION
This Instruction is used to measure voltage at a
single-ended input with respect to ground.
Output is in millivolts.
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
2
03:
2
04:
4
05:
FP
06:
FP
Input locations altered: 1 per measurement
*** 2 DIFFERENTIAL VOLTS ***
FUNCTION
This Instruction reads the voltage difference
between the high and low inputs of a differential
channel. Table 9-1 contains all valid voltage
ranges and their codes. Both the high and low
inputs must be within ±2.5 V of the CR10's
ground (see Common Mode Range in Section
14.3.2). Pyranometer and thermopile sensors
require a jumper between LO and GROUND to
TABLE 9-1. Input Voltage Ranges and Codes
60 Hz
50 Hz
Reject
Reject
21
31
22
32
23
33
24
34
25
35
DESCRIPTION
Repetitions
Range code (Table 9-1)
Single-ended channel
number for first
measurement
input location for first
measurement
Multiplier
Offset
Full Scale Range
±2.5 mV
±7.5 mV
mV
±25
mV
±250
mV
333.
±2500
keep them in Common Mode Range. Output is
in millivolts.
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
2
03:
2
04:
4
05:
FP
06:
FP
Input locations altered: 1 per measurement
*** 3 PULSE COUNT ***
There are three pulse input types which may be
measured with the Pulse Count Instruction.
HIGH FREQUENCY PULSE
In this configuration, the minimum detectable
pulse width is 2 microseconds, i.e. the
maximum frequency is 250 kHz with a 50%
duty cycle. The 8 bit counter has a maximum
input frequency of 2000 Hz and the 16 bit
option a maximum of 250 kHz. The count is
incremented when input voltage changes from
below 1.5 volts to above 3.5 volts. The
Resolution*
0.33 µV
1.
µV
3.33 µV
33.3 µV
µV
DESCRIPTION
Repetitions
Range code (Table 9-1)
Differential channel
number for first
measurement
Input location for first
measurement
Multiplier
Offset
9-1