Thermocouple Type Codes; Voltage And Temperature Ranges For Thermocouples If The Reference Is 20°C - Campbell Measurement and Control Module CR10 Operator's Manual

Ds 70;
Hide thumbs Also See for Measurement and Control Module CR10:
Table of Contents

Advertisement

SECTION 9. INPUT/OUTPUT INSTRUCTIONS
Code
Thermocouple Type
X1
T (copper - constantan)
X2
E (chromel - constantan)
X3
K (chromel - alumel)
X4
J (iron - constantan)
TABLE 9-4. Voltage and Temperature Ranges for Thermocouples
Voltage
Range
Type T
±2.5 mV
±7.5 mV
-270 to 181
±25 mV
-270 to 400
±250 mV
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
2
03:
2
04:
2
05:
4
06:
4
07:
FP
08:
FP
Input locations altered: 1 for each
thermocouple channel
*** 14 THERMOCOUPLE TEMPERATURE,
***
DIFFERENTIAL MEASUREMENT
FUNCTION
This instruction calculates the thermocouple
temperature for the thermocouple type selected.
The instruction specifies a DIFFERENTIAL
VOLTAGE MEASUREMENT (Section 13.2) on
the thermocouple, adds the measured voltage to
the voltage calculated for the reference
temperature relative to 0°C, and converts the
combined voltage to temperature in °C. The
differential inputs are briefly shorted to ground
prior to making the voltage measurement to
insure that they are within the common mode
range. Table 9-3 gives the thermocouple type
codes for Parameter 4. Enter a 9 in front of the
9-8
TABLE 9-3. Thermocouple Type Codes
if the Reference is 20°C
Type E
-46 to 50
-21 to 60
-124 to 134
-270 to 365
−−−
-270 to 1000
DESCRIPTION
Repetitions
Range code (Table 9-4)
Single-ended channel
number for first TC
Thermocouple type
code
Reference temperature
location
Destination input
location
Multiplier
Offset
X = 0
Normal Measurement
X = 8
TC input from A5B40 isolation
(uses 5 V range)
X = 9
Output -99999 if out of common
mode range (Inst. 14 only)
Type K
-44 to 80
-270 to 620
-270 to 620
-270 to 1372
code and the CR10 will make an additional
check on common mode range; -99999 is output
for temperature if common mode range is
exceeded.
PARAM.
DATA
NUMBER
TYPE
01:
2
02:
2
03:
2
04:
2
05:
4
06:
4
07:
FP
08:
FP
Input locations altered: 1 for each
thermocouple channel
*** 16 TEMPERATURE FROM ***
PLATINUM R.T.D.
FUNCTION
This instruction uses the result of a previous
RTD bridge measurement to calculate the
temperature according to the DIN 43760
specification adjusted (1980) to conform to the
International Electrotechnical Commission
standard. The range of linearization is -200° to
850°C. The error in the linearization is less
than 0.001°C between -100° and +300°C, and
is less than 0.003°C between -180° and
+830°C. The error (T calculated - T standard)
Type J
-29 to 67
-149 to 159
-210 to 476
-210 to 760
DESCRIPTION
Repetitions
Range code (Table 9-1)
Differential channel
number for first TC
Thermocouple type
code
Reference temperature
location
Destination input
location
Multiplier
Offset