5. INSTALLATION
3) Output connection with down-voltage ISO transformer (Option)
110/115/120VAC
To have the 110/115/120Vac output, you may have to order the UPS system frame
with down-voltage ISO transformer. The output terminal block of down-voltage
transformer is at the lower section of the rear panel of the frame. It is recommended to
divide the total load as equally as possible between L1/N1 and L2/N2 for low voltage
output. However, the L1 and L2 terminals represent 220/230/240VAC.
Note
110VAC
Load
Current
2KVA
18.2 A
4KVA
36.4 A
6KVA
54.5 A
8KVA
72.7 A
10KVA
90.9 A
12KVA
109.1 A
14KVA
Not Allowed
16KVA
Not Allowed
18KVA
Not Allowed
20KVA
Not Allowed
22KVA
Not Allowed
24KVA
Not Allowed
220/230/240VAC
DO NOT connect the load over 12kVA on 110/115/120VAC terminal blocks. For safety,
it is recommended to install a breaker panel between the terminal block and the loads.
Please refer to below table for the output current ratings.
115VAC
Current
17.4 A
34.8 A
51.2A
69.6 A
87 A
104.4 A
Not Allowed Not Allowed
Not Allowed Not Allowed
Not Allowed Not Allowed
Not Allowed Not Allowed
Not Allowed Not Allowed
Not Allowed Not Allowed
110/115/120VAC
120VAC
220VAC
Current
Current
16.7 A
9.1 A
33.3 A
18.2 A
50 A
27.3 A
66.7 A
36.4 A
83.3 A
45.5 A
100 A
54.5 A
63.6 A
72.7 A
81.8 A
90.9 A
100 A
109.1 A
12
230Vac
240VAC
Current
Current
8.7 A
8.3 A
17.4 A
16.7 A
26.1 A
25 A
34.8 A
33.3 A
43.5 A
41.7 A
51.2A
50 A
60.9 A
58.3 A
69.6 A
66.7 A
78.3 A
75 A
87 A
83.3 A
95.7A
91.7 A
104.4 A
100 A