8
|
Electrical installation

8.3.2 To connect the backup heater power supply

Installer reference guide
84
1 2 3
a
A
B
A
B
X1M
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
3 Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect X11Y to X11YB. The necessity
of separate normal kWh rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
if preferential kWh rate power supply is interrupted when active, OR
if no power consumption of the indoor unit is allowed at the preferential kWh
rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/9+10) as the safety thermostat for the additional zone. It is only possible for
the system to have EITHER preferential kWh rate power supply OR a safety
thermostat for the additional zone.
Backup heater type
*3V
1N~, 50 Hz,
230 V AC, 6.3 A
L
N
6
5
b
a
b
c
5 6
1 2 3
X11YB
X2M
X11YA
X11Y
X1A
Power supply
1N~ 230 V
S1S
9
10
c
9 10
X5M
Wires
2+GND
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10