Daikin Altherma 3 R F Installer's Reference Manual page 190

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
A.8
[3-00]
Is auto restart of the unit allowed?
A.8
[3-01]
--
A.8
[3-02]
--
A.8
[3-03]
--
A.8
[3-04]
--
A.8
[3-05]
--
A.8
[3-06]
What is the maximum desired room temperature in heating?
A.8
[3-07]
What is the mimimum desired room temperature in heating?
A.8
[3-08]
What is the maximum desired room temperature in cooling? (*)
A.8
[3-09]
What is the minimum desired room temperature in cooling? (*)
A.8
[4-00]
What is the BUH operation mode?
A.8
[4-01]
Which electric heater has priority?
A.8
[4-02]
Below which outdoor temperature is heating allowed?
A.8
[4-03]
--
A.8
[4-04]
Is the pump allowed during pipe freeze prevention?
A.8
[4-05]
--
A.8
[4-06]
Emergency
A.8
[4-08]
Which power limitation mode is required on the system?
A.8
[4-09]
Which power limitation type is required?
A.8
[4-0A]
--
A.8
[4-0B]
Automatic cooling/heating changeover hysteresis. (*)
A.8
[4-0D]
Automatic cooling/heating changeover offset. (*)
A.8
[5-00]
Is backup heater operation allowed above equilibrium temperature during space
heating operation?
A.8
[5-01]
What is the equilibrium temperature for the building?
A.8
[5-02]
Space heating priority.
A.8
[5-03]
Space heating priority temperature.
A.8
[5-04]
Set point correction for domestic hot water temperature.
A.8
[5-05]
What is the requested limit for DI1?
A.8
[5-06]
What is the requested limit for DI2?
A.8
[5-07]
What is the requested limit for DI3?
A.8
[5-08]
What is the requested limit for DI4?
A.8
[5-09]
What is the requested limit for DI1?
A.8
[5-0A]
What is the requested limit for DI2?
A.8
[5-0B]
What is the requested limit for DI3?
A.8
[5-0C]
What is the requested limit for DI4?
A.8
[5-0D]
--
A.8
[5-0E]
--
A.8
[6-00]
The temperature difference determining the heat pump ON temperature.
A.8
[6-01]
The temperature difference determining the heat pump OFF temperature.
A.8
[6-02]
--
A.8
[6-03]
--
A.8
[6-04]
--
A.8
[6-05]
--
A.8
[6-06]
--
A.8
[6-07]
--
A.8
[6-08]
What is the hysteresis to be used in reheat mode?
A.8
[6-09]
--
A.8
[6-0A]
What is the desired comfort storage temperature?
A.8
[6-0B]
What is the desired eco storage temperature?
A.8
[6-0C]
What is the desired reheat temperature?
A.8
[6-0D]
What is the desired DHW production type?
A.8
[6-0E]
What is the maximum temperature setpoint?
A.8
[7-00]
--
A.8
[7-01]
--
A.8
[7-02]
How many leaving water temperature zones are there?
A.8
[7-03]
--
A.8
[7-04]
--
A.8
[7-05]
Boiler efficiency
A.8
[8-00]
Minimum running time for domestic hot water operation.
A.8
[8-01]
Maximum running time for domestic hot water operation.
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/O
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(*) Setting is not applicable for this unit
Range, step
Default value
0: No
1: Yes
0
1
4
2
1
18~30°C, step: 0,5°C
30°C
12~18°C, step: 0,5°C
12°C
25~35°C, step: 0,5°C
35°C
15~25°C, step: 0,5°C
15°C
0: Disabled
1: Enabled
2: Only DHW
0: None
1: -
2: BUH
14~35°C, step: 1°C
22°C
3
0: intermittent pump operation
1: Continuous pump operation
2: OFF
0
0: Manual
1: Automatic
0: No limitation
1: Continuous
2: Digital inputs
0: Current
1: Power
0
1~10°C, step: 0,5°C
1°C
1~10°C, step: 0,5°C
3°C
0: Allowed
1: Not allowed
-15~35°C, step: 1°C
0°C
0: Disabled
1: Enabled
-15~35°C, step: 1°C
0°C
0~20°C, step: 1°C
10°C
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~50 A, step: 1 A
50 A
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0~20 kW, step: 0,5 kW
20 kW
0
1
2~40°C, step: 1°C
25°C
0~10°C, step: 1°C
2°C
0
0
0
0
0
0
2~20°C, step: 1°C
10°C
0
30~[6-0E]°C, step: 1°C
30~min(50, [6-0E])°C, step: 1°C
50°C
30~min(50, [6-0E])°C, step: 1°C
45°C
0: Reheat only
1: Reheat + sched.
2: Scheduled only
40~60°C, step: 1°C
60°C
0
2
0: 1 LWT zone
1: 2 LWT zones
2.5
0
0: Very high
1: High
2: Medium
3: Low
4: Very low
0~20 min, step 1 min
1 min
5~95 min, step: 5 min
30 min
5/7
Installer setting at variance with
default value
Date
Value
4P4596829-1 - 2019.10