Daikin Altherma 3 R F Installer's Reference Manual page 105

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
There are 2 leaving water temperature zones:
The zone with the lowest leaving water temperature (in heating) is called the
main leaving water temperature zone.
The zone with the highest leaving water temperature (in heating) is called the
additional leaving water temperature zone.
Remark: In practice, the main leaving water temperature zone consists of the
higher load heat emitters and a mixing station is installed to achieve the desired
leaving water temperature.
a
Additional LWT zone
b
Main LWT zone
c
Mixing station
Space heating: Pump operation mode
#
Code
[A.2.1.9]
[F-0D]
When the space heating control is OFF by the user interface, the pump is always
OFF. When the space heating control is ON, you can select the desired pump
operation mode (only applicable during space heating).
Continuous:
Continuous pump operation, regardless of thermo ON or OFF condition.
Remark: Continuous pump operation requires more energy than sample or
request pump operation.
a
b
c
b
c
d
a
Space heating control (user interface)
b
OFF
c
ON
d
Pump operation
Sample:
The pump is ON when there is a heating demand as the leaving water temperature
has not reached the desired temperature yet. When thermo OFF condition occurs,
the pump runs every 5  minutes to check the water temperature and demand
heating if necessary.
Remark: Sample is NOT available in external room thermostat control or room
thermostat control.
a
c
b
Description
Pump operation mode
0 (Continuous)
1 (Sample)
2 (Request)
9
Configuration
|
Installer reference guide
105