Daikin Altherma 3 R F Installer's Reference Manual page 153

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
2
Magnetic filter/dirt separator
a
b
c
d
a
Screw connection
b
Magnetic sleeve
c
Drain valve
d
Drain cap
The yearly maintenance of the magnetic filter/dirt separator consists of:
▪ Checking if both parts of the magnetic filter/dirt separator are still screwed
tight (a).
▪ Emptying the dirt separator as follows:
1 Take off the magnetic sleeve (b).
2 Unscrew the drain cap (d).
3 Connect a drain hose to the bottom of the water filter so that the water and
dirt can be collected in a suitable container (bottle, sink...).
4 Open the drain valve for a couple of seconds (c).
Result: Water and dirt will come out.
5 Close the drain valve.
6 Screw the drain cap back on.
7 Reattach the magnetic sleeve.
8 Check the pressure of the water circuit. If required, add water.
NOTICE
When checking the magnetic filter/dirt separator for tightness, hold it firmly, so
as NOT to apply stress to the water piping.
Do NOT isolate the magnetic filter/dirt separator by closing the shut‑off valves. To
properly empty the dirt separator, sufficient pressure is required.
To prevent dirt from remaining in the dirt separator, ALWAYS take off the
magnetic sleeve.
ALWAYS first unscrew the drain cap, and connect a drain hose to the bottom of
the water filter, then open the drain valve.
12
1
3
4
5
Maintenance and service
|
Installer reference guide
153

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehfz03s18dj3vErla03dav3