Installation manual
Daikin Altherma 3 R F
EHVH04SU18DA6V7
EHVH04SU23DA6V7
Installation manual
EHVH08SU18DA6V7
English
Daikin Altherma 3 R F
EHVH08SU23DA6V7

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma 3 R F

  • Page 1 Installation manual Daikin Altherma 3 R F EHVH04SU18DA6V7 EHVH04SU23DA6V7 Installation manual EHVH08SU18DA6V7 English Daikin Altherma 3 R F EHVH08SU23DA6V7...
  • Page 2 3P507286-10C...
  • Page 3: Table Of Contents

    Configuration wizard: System ........17 Latest revisions of the supplied documentation may be available on 5.2.4 Configuration wizard: Backup heater ......18 the regional Daikin website or via your dealer. 5.2.5 Configuration wizard: Main zone......... 19 5.2.6 Configuration wizard: Additional zone......20 The original documentation is written in English.
  • Page 4: About The Box

    ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). 2.2.1 To remove the accessories from the ▪ The full set of latest technical data is available on the Daikin domestic hot water tank kit Business Portal (authentication required). About the box...
  • Page 5: Preparation

    3 Preparation WARNING Preparation Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable Preparing the installation site legislation (for example national gas regulation) and are executed only by authorised persons. WARNING NOTICE The appliance shall be stored in a room without continuously operating ignition sources (example: open ▪...
  • Page 6 ▪ Top opening: The area of the top opening must be larger than or equal to the bottom opening. The bottom of the top opening must be situated at least 1.5 m above the top of the bottom opening. ▪ Ventilation openings to the outside are NOT considered suitable ventilation openings (the user can block them when it is cold). Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 7: Preparing Water Piping

    Switch box cover power supply (voltage Front panel free contact) High voltage switch box cover Normal kWh rate power 6.3 A Open supply 1 Remove the top panel. Optional equipment EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 8: To Lower The Switch Box On The Indoor Unit

    "4.1.2 To lower the switch box on the indoor drain" [ 4  9] ▪ "4.2.2 To connect the drain hose to the ▪ When you need access to the high voltage switch box Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 9: Mounting The Indoor Unit

    You can route the drain hose through the left or right side panel. Prerequisite: The user interface panel and front panel have been removed. 1 Remove one of the side panels. 2 Cut out the rubber grommet. EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 10: Connecting Water Piping

    Water inlet and water outlet 22 mm connection, discharge piping connection 15 mm Adaptor 22 mm×3/4" Female BSP T-piece 22 mm×22 mm×22 mm Expansion vessel of 18 L – 3/4" Male BSP Tundish 15 mm inlet, 22 mm outlet Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 11: To Connect The Recirculation Piping

    The following example shows discharge below fixed grating (Building Regulation G3 section 3.61 gives alternative points of discharge): 4 Reattach the top panel. EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 12: To Fill The Water Circuit

    3 Routing of the wiring inside the unit should be as follows. Fix 4 Seal the low voltage wiring intake using the sealing tape the cable to the cable rail using cable ties: (delivered as accessory). Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 13: To Connect The Main Power Supply

    Z less than or equal to Z 2 Fix the cables with cable ties to the cable tie mountings. Connect the backup heater power supply as follows: EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 14: To Connect The Shut-Off Valve

    SWB Switch box X6M Terminal (field supply) NOTICE Do NOT cut or remove the backup heater power supply cable. 2 Fix the cable with cable ties to the cable tie mountings. Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 15: To Connect The Alarm Output

    1 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. 9 10 2 Fix the cable with cable ties to the cable tie mountings. EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 16: Finishing The Indoor Unit Installation

    The configuration influences the following: ▪ The calculations of the software ▪ What you can see on and do with the user interface You can configure the system via the user interface. Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 17: Configuration Wizard

    When the heat pump fails to operate, the backup heater can serve as an emergency heater. It then takes over the heat load either automatically or by manual interaction. EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 18: Configuration Wizard: Backup Heater

    Voltage This can be set to: ▪ 230V, 1ph ▪ 230V, 3ph Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 19: Configuration Wizard: Main Zone

    50°C, Leaving water Unit operation is decided based on the leaving Daikin recommends NOT to disable the backup heater water temperature regardless the actual room second step because it will have a big impact on the...
  • Page 20: Configuration Wizard: Additional Zone

    X1 is equally higher as the preferred Schedule temperature at X2. Indicates if the desired leaving water temperature is according to a Slope zone" [ 4  19]. schedule. Also see "5.2.5 Configuration wizard: Main Offset Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 21: Configuration Wizard: Tank

    The tank will heat up until the storage comfort temperature has been reached. It is the higher desired temperature when a storage comfort action is scheduled. EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 22: Settings Menu

    ON/OFF condition. 5.3.2 Additional zone Thermostat type Only applicable in external room thermostat control. For more info zone" [ 4  22]. about the functionality, see "5.3.1 Main Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 23: Menu Structure: Overview Installer Settings

    Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 24: Commissioning

    The correct pipe size is installed and the pipes are above). However, if you purge air from the heat emitters or properly insulated. collectors, mind the following: There is NO water leak inside the indoor unit. Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 25: To Perform An Operation Test Run

    Hand-over to the user 2 Select OK to confirm. Once the test run is finished and the unit operates properly, please make sure the following is clear for the user: EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 26 ▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 27: Technical Data

    8 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). Piping diagram: Indoor unit...
  • Page 28: Wiring Diagram: Indoor Unit

    # Preferential kWh rate power supply contact * Heat pump convector # Electrical meter pulse input 1 * Digital I/O PCB # Electrical meter pulse input 2 * Demand PCB Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 29 12 V DC pulse detection (voltage thermostat thermostat supplied by PCB) supplied by PCB) Only for wireless On/OFF Only for wireless On/OFF 230 V AC supplied by PCB 230 V AC supplied by PCB thermostat thermostat EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 30 A8P: X801M: 4-5 demand input 4 signal 2 core Only for remote user interface 2x0.75 X5M: 11-12 A14P: P1-P2 user interface communication 2 core 2x0.75 A13P: P1-P2 LAN adapter communication 4D128739 Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 31: Indoor Unit

    15 min 26 sec EHVH04SU23DA6V7 195 l 20 min 06 sec indoor unit EHVH08SU18DA6V7 145 l 15 min 26 sec (kg) Minimum floor area (m²) EHVH08SU23DA6V7 195 l 20 min 06 sec H=600 mm 1.84 28.81 1.86 29.44 1.88 30.08 1.90 30.72 EHVH04+08SU18+23DA6V7 Installation manual Daikin Altherma 3 R F 4P619456-1 – 2020.03...
  • Page 32: Warning Label

    220 l 348 kg EHVH04SU23DA6V7 180 l 299 kg EHVH08SU18DA6V7 EHVH08SU23DA6V7 220 l 348 kg ■ Maximum design pressure: 10 bar 9.1 l ■ Rated volume heat exchanger: 4P616081-1 Installation manual EHVH04+08SU18+23DA6V7 Daikin Altherma 3 R F 4P619456-1 – 2020.03...