7.2.2 Formula to calculate the expansion vessel pre-pressure

7.2.3 To check the water volume and flow rate

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
Zn-coated parts. Never use zinc coated parts in the water circuit. Because the
internal water circuit of the unit uses copper piping, excessive corrosion may
occur.
Non-brass metallic piping. When using non-brass metallic piping, insulate the
brass and non-brass properly so that they do NOT make contact with each other.
This to prevent galvanic corrosion.
Valve – Change‑over time. When using a 2-way valve or a 3-way valve in the
water circuit, the maximum change-over time of the valve must be 60 seconds.
Domestic hot water tank – Capacity. To avoid stagnation of water, it is
important that the storage capacity of the domestic hot water tank meets the
daily consumption of domestic hot water.
Domestic hot water tank – After installation. Immediately after installation, the
domestic hot water tank must be flushed with fresh water. This procedure must
be repeated at least once a day the first 5 consecutive days after installation.
Domestic hot water tank – Standstills. In cases where during longer periods of
time there is no consumption of hot water, the equipment MUST be flushed with
fresh water before usage.
Domestic hot water tank – Disinfection. For the disinfection function of the
domestic hot water tank, see
4
advanced" [
 123].
Thermostatic mixing valves. In accordance with the applicable legislation, it may
be necessary to install thermostatic mixing valves.
Hygienic measures. The installation must be in compliance with the applicable
legislation and may require additional hygienic installation measures.
Recirculation pump. In accordance with the applicable legislation, it may be
required to connect a recirculation pump in between the hot water end point
and the recirculation connection of the domestic hot water tank.
a
b
a
Recirculation connection
b
Hot water connection
c
Shower
d
Recirculation pump
The pre-pressure (Pg) of the vessel depends on the installation height difference
(H):
Pg=0.3+(H/10) (bar)
The indoor unit has an expansion vessel of 10 litre with a factory-set pre-pressure
of 1 bar.
To make sure that the unit operates properly:
You must check the minimum and maximum water volume.
You might need to adjust the pre-pressure of the expansion vessel.