Daikin Altherma 3 R F Installer's Reference Manual page 111

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
Leaving water temperature: Additional zone
#
[A.3.1.2.1]
N/A
[7.7.2.1]
[0-00]
[0-01]
[0-02]
[0-03]
(a)
Also see
"9.3 Weather-dependent
Leaving water temperature: Delta T source
The Delta T is the required temperature difference between entering and leaving
water. This applies to both temperature zones. Change the value of Delta T if
another minimum temperature difference is required for the good operation of the
heat emitters in heating mode.
#
[A.3.1.3.1]
[1-0B]
Leaving water temperature: Modulation
To allow better matching of the heat  pump capacity with the actual required
capacity, enable the leaving water temperature modulation. If modulation is
enabled, the unit calculates the leaving water temperature according to the
difference between desired and actual room temperature. As a result, the
heat pump will have less start/stop cycles and thus operate more economical.
If modulation is enabled, you can also set the maximum modulation of the leaving
water temperature. The maximum modulation is the value by which the desired
leaving water temperature is increased or lowered.
Code
Select the setpoint mode of the leaving water
temperature.
LWT setpoint mode:
0 (Fixed): Absolute
1 (Weather dep.): Weather-dependent
2
(Fixed/scheduled):
scheduled
method=LWT control)
3 (WD/scheduled): Weather-dependent +
scheduled
method=LWT control)
If you selected weather-dependent curve as a
setpoint mode, adjust the curve to your needs.
(a)
Set weather-dependent heating:
T t
[0-01]
[0-00]
[0-03]
T
:
Target
t
(additional)
T
: Outdoor temperature
a
curve" [
Code
Delta T for heating
Range: 3°C~10°C
9
Configuration
|
Description
Absolute
(only
if
Unit
(only
if
Unit
[0-02]
T a
leaving
water
temperature
4
 114].
Description
Installer reference guide
+
control
control
111

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehfz03s18dj3vErla03dav3

Table of Contents