Daikin Altherma 3 R F Installer's Reference Manual page 125

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
#
Code
[A.4.7]
[0-0E]
[0-0D]
[0-0C]
[0-0B]
Also see
"9.3  Weather-dependent curve" 
weather-dependent curves.
Heat pump operation
#
Code
N/A
[6-00]
N/A
[6-01]
Example: setpoint (T
)>maximum heat pump temperature–[6‑01]
U
T
DHW
T
= T
60
U
BUH OFF
T
50
HP MAX
T
48
HP OFF
46
T
HP ON
40
30
20
HP
10
5
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by the backup heater can
take place.
BUH
Backup heater
Description
Weather-dependent curve
T
DHW
[0-0C]
[0-0B]
T
[0-0E]
[0-0D]
T
: The desired tank temperature.
DHW
T
:
The
(averaged)
a
temperature
[0-0E]: low outdoor ambient temperature: –
40°C~5°C
[0-0D]: high outdoor ambient temperature:
10°C~25°C
[0-0C]: desired tank temperature when the
outdoor temperature equals or drops below
the low ambient temperature: 45°C~[6‑0E]°C
[0-0B]: desired tank temperature when the
outdoor temperature equals or rises above the
high ambient temperature: 35°C~[6‑0E]°C
4
[
  114] for more information about
Description
The temperature difference determining the heat
pump ON temperature.
2°C~40°C
The temperature difference determining the heat
pump OFF temperature.
0°C~10°C
[6-01]
[6-00]
T
= 60°C
U
T
= 50°C
HP MAX
HP
BUH
[6-01] =
2°C
[6-00] =
2°C
9
Configuration
|
a
outdoor
ambient
t
Installer reference guide
125