To perform a manual air purge
To perform an automatic air purge

10.4.3 To perform a test run

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
INFORMATION
When purging the main zone, make sure the setpoint for the main zone is at least
5°C higher than the actual water temperature inside the unit.
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See
4
to
Installer" [
 99].
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Manual and press
4 Go to [A.7.3.4]
purge > Start air purge and press
Result: The manual air purge starts and the following screen appears.
5 Use the and buttons to set the desired pump speed.
Result: Low
Result: High
INFORMATION
When purging the main zone, make sure the setpoint for the main zone is at least
5°C higher than the actual water temperature inside the unit.
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See
4
to
Installer" [
 99].
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Automatic and press
4 Go to [A.7.3.4]
purge > Start air purge and press
Result: Air purging will start and the following screen will be shown.
INFORMATION
The test run only applies to the additional temperature zone.
Prerequisite: Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See
4
to
Installer" [
 99].
2 Go to [A.7.1]:
> Installer settings > Commissioning > Test run.
3 Select a test and press
.
> Installer
settings > Commissioning > Air
to start the air purge function.
.
> Installer
settings > Commissioning > Air
to start the air purge function.
. Example: Heating.
10
Commissioning
|
"To set the user permission level
> Installer
settings >
"To set the user permission level
> Installer
settings >
"To set the user permission level
Installer reference guide
145