Connecting Water Piping; About Connecting The Water Piping; Precautions When Connecting The Water Piping; To Connect The Water Piping - Daikin Altherma 3 R F Installer's Reference Manual

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

7.6 Connecting water piping

7.6.1 About connecting the water piping

7.6.2 Precautions when connecting the water piping

7.6.3 To connect the water piping

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant
charge of the unit is indicated both in weight and CO
Formula to calculate the quantity in CO
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label. That GWP is based on
the current legislation on fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.
2 Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.
Before connecting the water piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the water piping typically consists of the following stages:
1
Connecting the water piping to the indoor unit.
2
Connecting the recirculation piping.
3
Connecting the drain hose to the drain.
4
Filling the water circuit.
5
Filling the domestic hot water tank.
6
Insulating the water piping.
INFORMATION
Also read the precautions and requirements in the following chapters:
"1 General safety
"7.2 Preparing water
NOTICE
Do NOT use excessive force when connecting the piping. Deformation of the piping
can cause malfunctioning of the unit.
To facilitate service and maintenance, 4 shut-off valves and 1 overpressure bypass
valve are provided. Mount the shut-off valves on the space heating water inlets
and space heating water outlets. To ensure the minimum flow rate (and prevent
overpressure), install the overpressure bypass valve on the space heating water
outlet for the additional zone.
equivalent tonnes: GWP value of the
2
4
precautions" [
 6]
4
piping" [
 54]
7
Piping installation
|
equivalent.
2
Installer reference guide
71

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehfz03s18dj3vErla03dav3