Daikin Altherma 3 R F Installer's Reference Manual page 191

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

6/7
Field settings table
Breadcrumb
Field code
Setting name
A.8
[8-02]
Anti-recycling time.
A.8
[8-03]
--
A.8
[8-04]
--
A.8
[8-05]
Allow modulation of the LWT to control the room temp?
A.8
[8-06]
Leaving water temperature maximum modulation.
A.8
[8-07]
What is the desired comfort main LWT in cooling? (*)
A.8
[8-08]
What is the desired eco main LWT in cooling? (*)
A.8
[8-09]
What is the desired comfort main LWT in heating?
A.8
[8-0A]
What is the desired eco main LWT in heating?
A.8
[8-0B]
--
A.8
[8-0C]
--
A.8
[8-0D]
--
A.8
[8-0E]
What is the ambient temp for BUH only operation?
A.8
[9-00]
What is the maximum desired LWT for main zone in heating?
A.8
[9-01]
What is the mimimum desired LWT for main zone in heating?
A.8
[9-02]
What is the maximum desired LWT for main zone in cooling? (*)
A.8
[9-03]
What is the mimimum desired LWT for main zone in cooling? (*)
A.8
[9-04]
Leaving water temperature overshoot temperature.
A.8
[9-05]
What is the mimimum desired LWT for add. zone in heating?
A.8
[9-06]
What is the maximum desired LWT for add. zone in heating?
A.8
[9-07]
What is the mimimum desired LWT for add. zone in cooling? (*)
A.8
[9-08]
What is the maximum desired LWT for add. zone in cooling? (*)
A.8
[9-0C]
Room temperature hysteresis.
A.8
[9-0D]
Pump speed limitation
A.8
[9-0E]
Pump speed limitation additional Zone
A.8
[C-00]
--
A.8
[C-01]
--
A.8
[C-02]
Is an external backup heat source connected?
A.8
[C-03]
Bivalent activation temperature.
A.8
[C-04]
Bivalent hysteresis temperature.
A.8
[C-05]
What is the thermo request contact type for the main zone?
A.8
[C-06]
What is the thermo request contact type for the add. zone?
A.8
[C-07]
What is the unit control method in space operation?
A.8
[C-08]
Which type of external sensor is installed?
A.8
[C-09]
What is the required alarm output contact type?
A.8
[C-0A]
--
A.8
[C-0C]
--
A.8
[C-0D]
--
A.8
[C-0E]
--
A.8
[D-00]
Which heaters are permitted if prefer. kWh rate PS is cut?
A.8
[D-01]
Contact type of preferential kWh rate PS installation?
A.8
[D-02]
Which type of DHW pump is installed?
A.8
[D-03]
Leaving water temperature compensation around 0°C.
A.8
[D-04]
Is a demand PCB connected?
A.8
[D-05]
Is the pump allowed to run if prefer. kWh rate PS is cut?
A.8
[D-07]
Is a solar kit connected?
A.8
[D-08]
Is an external kWh meter used for power measurement?
4P596829-1 - 2019.10
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
(*) Setting is not applicable for this unit
Range, step
Default value
0~10 hour, step: 0,5 hour
0,5 hour
50
95
0: No
1: Yes
0~10°C, step: 1°C
5°C
[9-03]~[9-02], step: 1°C
18°C
[9-03]~[9-02], step: 1°C
20°C
[9-01]~[9-00]°C, step: 1°C
35°C
[9-01]~[9-00]°C, step: 1°C
33°C
13
10
16
-15~25°C, step: 1°C
-7°C
37~60°C, step: 1°C
55°C
15~37°C, step: 1°C
25°C
18~22°C, step: 1°C
22°C
5~18°C, step: 1°C
5°C
1~4°C, step: 1°C
1°C
15~37°C, step: 1°C
25°C
37~55, step: 1°C
55°C
5~18°C, step: 1°C
5°C
18~22°C, step: 1°C
22°C
1~6°C, step: 0,5°C
1 °C
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
0
0
0: No
1: Bivalent
-25~25°C, step: 1°C
0°C
2~10°C, step 1°C
3°C
0: -
1: 1 contact
2: 2 contacts
0: -
1: 1 contact
2: 2 contacts
0: LWT control
1: Ext RT control
2: RT control
0: No
1: Outdoor sensor
2: Room sensor
0: Normally open
1: Normally closed
0
0
0
0
0: None
1: -
2: BUH only
3: -
0: No
1: Active open
2: Active closed
3: Safety thermostat
0: No
1: Secondary rtrn
2: Disinf. Shunt
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
0: No
1: Pwr consmp ctrl
0: Forced off
1: As normal
0: No
1: Yes
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
Installer setting at variance with
default value
Date
Value

Hide quick links: