To Connect The Main Power Supply; To Connect The Backup Heater Power Supply - Daikin Altherma EPGA16DAV3 Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EPGA16DAV3:
Table of Contents

Advertisement

Routing
Possible cables (depending on unit type
and installed options)
c
▪ Heat pump convector (option)
High voltage control
▪ Room thermostat (option)
signal
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Alarm output
▪ Changeover to external heat source
control
▪ Space heating operation control
d
▪ Power supply for backup heater
High voltage power
supply (factory-
mounted cable)
CAUTION
Do NOT push or place redundant cable length in the unit.
4 Seal the low voltage wiring intake using the sealing tape
(delivered as accessory).
Without low voltage cables
7.6.8

To connect the main power supply

1 Connect the main power supply.
In case of normal kWh rate power supply
1 2 3
1 2 3
a
1 2 3
X2M
X11YB
X11YA
X1M
X11Y
X1A
Legend: see illustration below.
In case of preferential kWh rate power supply
Connect X11Y to X11YB.
EPGA11~16DAV3 + EAVZ16S18+23DA6V+9W
Daikin Altherma – Low temperature split
4P556075-1 – 2019.02
With low voltage cables
X5M
A5P
1 2 3
N L
1
2 3
N L
a
b
c
1 2 3
5
6
X2M
X11YB
X1M
X11YA
X11Y
X1A
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
2 Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect
X11Y to X11YB. The necessity of separate normal kWh
rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat for the additional zone. It is only possible for the
system to have EITHER preferential kWh rate power
supply OR a safety thermostat for the additional zone.
7.6.9
To connect the backup heater power
supply
WARNING
The backup heater MUST have a dedicated power supply
and MUST be protected by the safety devices required by
the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, always
connect the backup heater power supply and the earth
cable.
The backup heater capacity can vary, depending on the indoor unit
model. Make sure that the power supply is in accordance with the
backup heater capacity, as listed in the table below.
7 Installation
S1S
9 10
X5M
A5P
Installer reference guide
33

Advertisement

Table of Contents
loading

Table of Contents