Opening and closing the units ............................43 6.2.1 About opening the units..........................43 6.2.2 To open the outdoor unit..........................43 6.2.3 To close the outdoor unit..........................43 Installer reference guide ERLA03DAV3 + EHFZ03S18DJ3V Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 3
To connect the electrical wiring to the outdoor unit ..................79 Connections to the indoor unit ............................80 8.3.1 To connect the main power supply........................ 82 ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 4
Symptom: The system is making gurgling noises after commissioning ............161 13.3.4 Symptom: The pump is blocked........................162 13.3.5 Symptom: The pump is making noise (cavitation)..................162 13.3.6 Symptom: The pressure relief valve opens....................162 Installer reference guide ERLA03DAV3 + EHFZ03S18DJ3V Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 5
Piping diagram: Indoor unit ............................176 15.3 Wiring diagram: Outdoor unit ............................177 15.4 Wiring diagram: Indoor unit ............................179 16 Glossary 17 Field settings table ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Indicates a situation that could result in death or serious injury. WARNING: FLAMMABLE MATERIAL CAUTION Indicates a situation that could result in minor or moderate injury. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
▪ In places where there is a risk of fire due to the leakage of flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Use a vacuum pump to evacuate the installation. NOTICE After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If applicable. See the installation manual or installer reference guide of your application for more information. WARNING The selection of the brine MUST be in accordance with the applicable legislation. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 12
Install power cables at least 1 m away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 m may not be sufficient. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 13
Running the product in reversed phase can break the compressor and other parts. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Format: Paper (in the box of the indoor unit) + Digital files on http:// www.daikineurope.com/support-and-manuals/product-information/ Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer. The original documentation is written in English. All other languages are translations. ERLA03DAV3 + EHFZ03S18DJ3V...
About the documentation Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Page 16
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Keep the unit upright in order to avoid damage. ▪ Prepare the path along which you want to bring the unit inside in advance. 3.2 Outdoor unit 3.2.1 To unpack the outdoor unit ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Drain plug (located on the bottom of the packing case) Energy label Fluorinated greenhouse gases label 3.3 Indoor unit 3.3.1 To unpack the indoor unit 8× ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Handles at the back of the unit Handles at the bottom of the unit. Carefully tilt the unit to the back so that the handles become visible. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Model identification Example: ER L A 03 DA V3 Code Explanation European split outdoor pair heat pump Low water temperature – ambient zone: −10~−20°C Refrigerant R32 Capacity class Model series Power supply ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
"6.1.2 Additional installation site requirements of the outdoor unit in cold climates" [ 40] for more information. ▪ For installation instructions, see the installation manual of the bottom plate heater. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
The remote indoor sensor can only be used in case the user interface is configured with room thermostat functionality. ▪ You can only connect either the remote indoor sensor or the remote outdoor sensor. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 23
LAN adapter for smartphone control (BRP069A62) You can install this LAN adapter to control the system via a smartphone app. For installation instructions, see the installation manual of the LAN adapter. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
How many rooms are heated by the heat pump system? ▪ Which heat emitter types are used in each room and what is their design leaving water temperature? ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Heat pump convectors: 45°C Setup Additional leaving water temperature zone Room 1 Room 2 Main leaving water temperature zone Room 3 Remote controller of the heat pump convectors ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 26
Depending on the demand, the indoor unit supplies different leaving water temperature matching the design temperature of the different heat emitters. Underfloor heating has the best performance with the heat pump system. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Example: If the DHW consumption for 2 persons per day is as follows: ▪ 1 showers ▪ 1 bath ▪ 2 sink volumes Then the DHW consumption = (1×100 l)+(1×150 l)+(2×10 l)=270 l ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Thermodynamic cycle of the heat pump Electrical backup heater ▪ For more information about optimizing the energy consumption for producing domestic hot water, see "9 Configuration" [ 98]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
The DHW pump is field-supplied and its installation is the responsibility of the installer. For the electrical wiring, see "8.3.6 To connect the domestic hot water pump" [ 89]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
▪ Setup and configuration: No additional equipment needed. 5.4.2 Consumed energy You can use the following methods to determine the consumed energy: ▪ Calculating ▪ Measuring ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Single-phase outdoor unit Single-phase ▪ Backup heater supplied from a single- phase grid (i.e. the backup heater model is *3V connected to a single- phase grid) ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Power meter 2: Measures the rest (i.e. indoor unit and backup heater). Setup ▪ Connect power meter 1 to X5M/5 and X5M/6. ▪ Connect power meter 2 to X5M/3 and X5M/4. "8.3.5 To connect the electricity meters" [ 88]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Defrost operation. Otherwise, if defrosting is interrupted several times, the heat exchanger will freeze up. ▪ Space heating and DHW production by allowing the backup heater step 1. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
5.5.2 Power limitation activated by digital inputs Power limitation is also useful in combination with an energy management system. The power or current of the entire Daikin system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following: ▪...
If this is NOT possible, we recommend to connect a remote indoor sensor (option KRCS01-1). ▪ Setup: For installation instructions, see the installation manual of the remote indoor sensor. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 36
To protect the outdoor unit, the internal sensor of the outdoor unit is always used. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
(example: open flames, an operating gas appliance or an operating electric heater). WARNING DO NOT reuse refrigerant piping that has been used with any other refrigerant. Replace the refrigerant pipes or clean thoroughly. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
It is recommended to install a baffle plate when the air outlet is exposed to wind. It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 39
If the outdoor unit is exposed to direct sea winds, install a windbreaker. ▪ Height of windbreaker≥1.5×height of outdoor unit ▪ Mind the service space requirements when installing the windbreaker. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
([8-0E]) field setting. This setting can also be changed via the menu structure. See the installation manual of the indoor unit for how to change the setting. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If you have limited installation space, do the following before installing the unit in its final position: "6.4.4 To connect the drain hose to the drain" 51]. It requires to remove one or both side panels. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 42
WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. NOTICE ▪...
DANGER: RISK OF BURNING 1× 6.2.3 To close the outdoor unit NOTICE When closing the outdoor unit cover, make sure that the tightening torque does NOT exceed 1.3 N•m. 1× ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
1 Remove the top panel. 7× 2 Remove the upper front panel. Open the hinges at the top and slide the top panel upwards. 3 Remove the switch box cover. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 45
▪ When you need access to the high voltage switch box 2× 5 If you need access to the high voltage components, remove the high voltage switch box cover. 4× ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
5 Reinstall the front panel. 6 Reinstall the upper front panel. NOTICE When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Fix the unit securely by means of foundation bolts in accordance with the foundation drawing. Prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If you install the unit on a frame, install a waterproof plate within 150 mm of the bottom side of the unit in order to prevent water from getting into the unit and to avoid drain water dripping (see the following figure). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
3 Insert a rubber sheet between the cables and the outdoor unit to prevent the cables from scratching the paint (field supply). 4 Attach the ends of the cables. 5 Tighten the cables. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
4 Adjust the height of the leveling feet to compensate for floor irregularities. The maximum allowed deviation is 1°. ≤1° NOTICE Do NOT tilt the unit forwards: 1° 1° 0° ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
It is recommended to use a tundish to collect the water. Option 1: Through the left side panel 3× Option 2: Through the right side panel 3× ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
1 Insulate and fix the refrigerant piping and cables as follows: Gas pipe Gas pipe insulation Interconnection cable Field wiring (if applicable) Liquid pipe Liquid pipe insulation Finishing tape 2 Install the service cover. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Deformation of the piping can cause malfunctioning of the unit. ▪ Connecting piping – Tools. Only use appropriate tooling to handle brass, which is a soft material. If NOT, pipes will get damaged. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 55
Water temperature. All installed piping and piping accessories (valve, connections,…) MUST withstand the following temperatures: INFORMATION The following illustration is an example and might NOT match your system layout. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 56
Two automatic air purges are provided in the indoor unit. Check that the air purges are NOT tightened too much, so that automatic release of air in the water circuit is possible. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
To make sure that the unit operates properly: ▪ You must check the minimum and maximum water volume. ▪ You might need to adjust the pre-pressure of the expansion vessel. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 58
Use the following graph to determine the maximum water volume for the calculated pre-pressure. Pre-pressure (bar) Maximum water volume (l) Example: Maximum water volume and expansion vessel pre-pressure ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
"10.4 Checklist during commissioning" [ 143]. 7.2.4 Changing the pre-pressure of the expansion vessel NOTICE Only a licensed installer may adjust the pre-pressure of the expansion vessel. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
7.3 Connecting the refrigerant piping 7.3.1 About connecting the refrigerant piping Before connecting the refrigerant piping Make sure the outdoor and indoor unit are mounted. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Protect the piping as described in the following table to prevent dirt, liquid or dust from entering the piping. ▪ Use caution when passing copper tubes through walls (see figure below). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage. ▪ Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Part to be brazed Taping Manual valve Pressure-reducing valve Nitrogen ▪ Do NOT use anti-oxidants when brazing pipe joints. Residue can clog pipes and break equipment. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Piping protection. Protect the field piping against physical damage. 1 Connect the liquid refrigerant connection from the indoor unit to the liquid stop valve of the outdoor unit. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Before checking the refrigerant piping Make sure the refrigerant piping is connected between the outdoor unit and the indoor unit. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
200 kPa (2 bar). It is recommended to pressurize to 3000 kPa (30 bar) in order to detect small leaks. 2 Check for leaks by applying the bubble test solution to all connections. 3 Discharge all nitrogen gas. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
NOT increase. This might be caused by e.g. the closed state of the expansion valve in the outdoor unit circuit, but does NOT present any problem for correct operation of the unit. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
× total refrigerant charge [in kg] / 1000 Please contact your installer for more information. WARNING: FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Additional refrigerant amount charged Total refrigerant charge Quantity of fluorinated greenhouse gases of the total refrigerant charge expressed as tonnes CO equivalent. GWP = Global warming potential ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
To ensure the minimum flow rate (and prevent overpressure), install the overpressure bypass valve on the space heating water outlet for the additional zone. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 72
Mind the minimum flow rate when adjusting the overpressure bypass valve setting. "7.2.3 To check the water volume and flow rate" [ 57] and "10.4.1 To check the minimum flow rate" [ 143]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
2 Cut out the rubber grommet on top of the unit, and remove the stop. The recirculation connector is placed below the hole. 3 Route the recirculation piping through the grommet and connect it to the recirculation connector. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Connecting the electrical wiring typically consists of the following stages: ▪ "8.2 Connections to the outdoor unit" [ 79] ▪ "8.3 Connections to the indoor unit" [ 80] 8.1.1 Precautions when connecting the electrical wiring DANGER: RISK OF ELECTROCUTION ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool. Stranded conductor wire Round crimp-style terminal ▪ Use the following methods for installing wires: ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Must comply with applicable legislation Interconnection cable Minimum cable section of 1.5 mm² and applicable for 230 V Recommended field 16 A fuse Earth leakage circuit Must comply with applicable legislation breaker ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
At that moment, the outdoor unit compressor will not operate. The wiring to the unit is different depending on whether the power supply is interrupted or not. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
8.2.1 To connect the electrical wiring to the outdoor unit 1 Remove the service cover. See "6.2.2 To open the outdoor unit" [ 43]. 2 Strip insulation (20 mm) from the wires. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Space heating operation "8.3.8 To connect the space heating ON/OFF control output" [ 91]. Changeover to external "8.3.9 To connect the changeover to external heat source control heat source" [ 92]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 81
Maximum running current: 100 mA For the main zone: ▪ [A.2.1.7] Unit control method ▪ [A.2.2.4] Contact type main For the additional zone: ▪ [A.2.2.5] Contact type add. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Maximum length: 200 m "LAN adapter – System requirements" [ 82] LAN adapter – System requirements The requirements posed on the Daikin Altherma system depend on the LAN adapter application/system layout (app control): Item Requirement LAN adapter software It is recommended to ALWAYS keep the LAN adapter software up-to-date.
Page 83
16 V DC detection (voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. [A.2.2.E.3] Preferential kWh rate Connect X11Y to X11YB. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
EITHER preferential kWh rate power supply OR a safety thermostat for the additional zone. 8.3.2 To connect the backup heater power supply Backup heater type Power supply Wires 1N~ 230 V 2+GND ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 85
Factory-mounted cable connected to the contactor of the backup heater, inside the switch box (K1M) Field wiring (see table below) Model (power supply) Connections to backup heater power supply *3V (1N~ 230 V) SWB2 Q1DI 1N~, 50 Hz 230 V AC ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
3 Upper switch box cover 2 Connect the user interface cable to the indoor unit. Fix the cable with cable ties to the cable tie mountings. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
6 Reinstall the faceplate onto the wallplate. Be careful NOT to pinch the wiring when attaching the frontplate to the unit. 8.3.4 To connect the shut-off valve Wires: 2×0.75 mm² Maximum running current: 100 mA 230 V AC supplied by PCB ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A (continuous) [A.2.2] Options > [A.2.2.A] DHW pump [7.3] Set schedules > [7.3.7] DHW pump 1 Open the following (see "6.2.4 To open the indoor unit" [ 44]): ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
1 Top panel 2 Upper front panel 3 Upper switch box cover 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
2 Upper front panel 3 Upper switch box cover 2 Connect the space heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
2 Upper front panel 3 Upper switch box cover 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
2 Upper front panel 3 Upper switch box cover 2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
3 Upper switch box cover Main zone Wires: 2×0.75 mm² — 2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 95
15 V DC, 10 mA. [A.2.1.6]=3 (Forced off contact = Thermostat) 4 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
8.4 After connecting the electrical wiring to the indoor unit To prevent water ingress to the switch box, seal the low voltage wiring intake using the sealing tape (delivered as accessory). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 97
Electrical installation Without low voltage cables With low voltage cables ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
When the installer settings are changed, the user interface will request to confirm. When confirmed, the screen will shortly turn OFF and "busy" will be displayed for several seconds. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If you do NOT press any button for more than 1 hour 9.1.2 To access the most used commands To access the installer settings 1 Set the user permission level to Installer. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 100
7 At installer settings menu, press to confirm the settings. Installer settings The system will restart. Cancel Confirm Adjust Result: The system will restart. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Result: All data (languages, schedules etc.) will be copied from the selected source user interface to the other one. When done, the system is ready to be operated via both user interfaces. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Confirm layout Please confirm the system layout. The system will restart and will be ready for first startup. Cancel Confirm Adjust Result: The user interface reinitializes. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
▪ 0 (At unit) ▪ 1 (In room) Only applicable if there are 2 user interfaces (1 installed in the room, 1 installed at the indoor unit). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 104
1 LWT zone: There is only 1 leaving water temperature zone. This zone is called the main leaving water temperature zone. Main LWT zone 2 LWT zones: ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 105
5 minutes to check the water temperature and demand heating if necessary. Remark: Sample is NOT available in external room thermostat control or room thermostat control. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
It runs when the disinfection function of the domestic hot water tank is running. No further settings are needed. See also illustrations below. See also: ▪ "5.3.4 DHW pump for instant hot water" [ 29] ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 107
External room thermostat at additional zone ▪ [C‑07]=1 (Ext RT control) User interface of the indoor unit External room thermostat at main zone External room thermostat at additional zone ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 108
The temperature sensor in the user interface is NOT used anymore. Remark: ; This value only has meaning in room thermostat control. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 109
(up to 2) power meters with different pulse frequencies. When only 1 or no power meter is used, select No to indicate the corresponding pulse input is NOT used. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
[1-01] [1-02] Set weather-dependent heating: [1-03] [1-02] [1-03] [1-00] [1-01] ▪ : Target leaving water temperature (main) ▪ : Outdoor temperature Also see "9.3 Weather-dependent curve" [ 114]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 111
If modulation is enabled, you can also set the maximum modulation of the leaving water temperature. The maximum modulation is the value by which the desired leaving water temperature is increased or lowered. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 112
The target delta T for the main zone depends on it. Code Description [A.3.1.1.7] [2-0C] Emitter type ▪ 0: Underfloor heat ▪ 1: Fancoil unit ▪ 2: Radiator ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
The maximum temperature is NOT applicable during disinfection function. See disinfection function. 9.2.6 Contact/helpdesk number Code Description [6.3.2] Number that users can call in case of problems. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Setpoint (X2, Y1) Example Set weather-dependent heating Confirm Adjust Scroll X1, X2 Examples of outdoor ambient temperature Y1, Y2 Examples of desired tank temperature or leaving water temperature ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
The purpose of this setting is to prevent selecting a wrong (i.e. too hot or too cold) leaving water temperature. Therefore the available desired heating temperature range and desired cooling temperature range can be configured. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 117
This function defines how much the water temperature may rise above the desired leaving water temperature before the compressor stops. The compressor will startup again when the leaving water temperature drops below the desired leaving water temperature. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 118
ONLY applicable in room thermostat control. In order to save energy by preventing overheating or undercooling the room, you can limit the range of the room temperature. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 119
Code Description Room temp. offset: Offset on the actual room temperature measured on the user interface sensor. [A.3.2.2] [2-0A] –5°C~5°C, step 0.5°C ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 120
Room frost protection ▪ 0: disabled ▪ 1: enabled [2-05] Room antifrost temperature 4°C~16°C INFORMATION If a U5 error occurs, room frost protection is NOT guaranteed, ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 121
When the leaving water temperature home page is ON and the external room thermostat is "Thermo ON", then room frost protection guaranteed by the normal logic. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 122
LWT zone. ▪ activate the On/OFF pump of the mixing valve station ONLY when there is demand. See "5 Application guidelines" [ 24]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Storage eco The storage economic temperature denotes the lower desired tank temperature. It is the desired temperature when a storage economic action is scheduled (preferably during day). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 124
In reheat mode, the desired tank temperature weather dependent. Note: When the displayed tank temperature is weather dependent, it cannot be adjusted on the user interface. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 125
[6-00] = 2°C Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by the backup heater can take place. Backup heater ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 126
Minimum time between two cycles for domestic hot water. Range: 0~10 hours Remark: The minimum time is 0.5 hours even when the selected value is 0. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
This setting is only overruled when backup heating is required during defrost operation or malfunctioning of the outdoor unit (when [A.6.C] is enabled). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 129
If a heat pump failure occurs and [A.6.C] is set to Manual, the room frost protection function, the underfloor heating screed dryout function, and the water pipe antifreeze function will remain active even if the user does NOT confirm emergency operation. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 130
Depending on the used boiler, this should be chosen as follows: Code Description [7‑05] Boiler efficiency ▪ 0: Very high ▪ 1: High ▪ 2: Medium ▪ 3: Low ▪ 4: Very low ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
CAUTION Make sure to observe all rules mentioned in application guideline 5 when bivalent operation function is enabled. Daikin shall NOT be held liable for any damage resulting from failure to observe this rule. Backup heater only ambient temperature The outdoor unit heat pump can operate until an ambient temperature of –7°C by default.
Page 132
Therefore, it is recommended to always enable the function. Code Description [A.6.1] [3‑00] Is the auto restart function of the unit allowed? ▪ 0: No ▪ 1: Yes ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 133
(via X2M/5-6) and the backup heater is NOT connected to the preferential kWh rate power supply. [D-05] Forced pump OFF : ▪ 0: Forced off ▪ 1: As normal ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 134
0 kW~20 kW, step 0.5 kW Amp. limits for DI: Only applicable in case of power limitation mode based on digital inputs and based on current values. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 135
The setting can be used to compensate for situations where the external outdoor ambient sensor cannot be installed on the ideal installation location (see installation). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 136
[9‑0D] define the maximum pump speed. In normal conditions, the default setting should NOT be modified. The pump speed limitation will be overruled when the flow rate is in the range of the minimum flow (error 7H). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 137
The maximum values depend on the unit type: [9-0D]=0 [9-0D]=5 a (kPa) a (kPa) b (l/min) b (l/min) [9-0D]=6 [9-0D]=7 a (kPa) a (kPa) b (l/min) b (l/min) ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 138
Configuration [9-0D]=8 a (kPa) b (l/min) External static pressure Water flow rate ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
[7.7.1] Main Additional Set weather-dependent heating [7.7.2] Additional Set weather-dependent heating INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
50 hours before reaching smooth operation and stable power consumption. NOTICE ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT, burning of the compressor might be the result. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
The air purge valve is open (at least 2 turns). The pressure relief valve purges water when opened. Clean water must come out. The domestic hot water tank is filled completely. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
ON), increase the flow until the additional pump is NOT assisting anymore (LED is OFF). 10 Go to [6.1.8]: > Information > Sensor information > Flow rate to check the flow rate. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
During air purge function, pump speed limitation [9‑0D] is NOT applicable. The air purge function automatically stops after 30 minutes. INFORMATION For best results, air purge each loop separately. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
"To set the user permission level Installer" [ 99]. 2 Go to [A.7.1]: > Installer settings > Commissioning > Test run. 3 Select a test and press . Example: Heating. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
The underfloor heating screed dryout function is active even if the user does NOT confirm emergency operation. ▪ During underfloor heating screed dryout, pump speed limitation [9‑0D] is NOT applicable. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 147
2 Go to [A.7.2]: > Installer settings > Commissioning > UFH screed dryout > Set dryout schedule. 3 Use the , and to program the schedule. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 148
"13.4 Solving problems based on error codes" [ 165]. To reset the U3 error, your User permission level needs to be Installer. 1 Go to the underfloor heating screed dryout screen. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 149
> Commissioning > UFH screed dryout > Dryout status > Stopped at and followed by the last executed step. 6 Modify and restart the execution of the program. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
NOTICE: Risk of electrostatic discharge Before performing any maintenance or service work, touch a metal part of the unit in order to eliminate static electricity and to protect the PCB. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Handle the water filters with care. Do NOT use excessive force when you reinsert the water filters so as NOT to damage the water filters mesh. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 153
▪ ALWAYS first unscrew the drain cap, and connect a drain hose to the bottom of the water filter, then open the drain valve. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 154
Using an ohmmeter, check if contactors K1M, K2M and K3M operate correctly. All contacts of these contactors must be in open position when the power is turned OFF. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
3 Remove the stop from the access point to the tank. 4 Use a drain hose and a pump to drain the tank via the access point. Access point to tank ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
12.5.2 To clean the water filter in case of trouble 1 Remove the water filter from the unit. See "12.5.1 To remove the water filter" [ 156]. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 157
Correctly install the strainer in the magnetic filter/dirt separator housing using the protrusions. Rolled‑up filter Strainer Protrusion 5 Install and properly tighten the bottom of the water filter housing. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Make sure to open the valve (if equipped) towards the expansion vessel, otherwise the overpressure will be generated. 5 Open the stop valves and add water to the water circuit if needed. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If you are unable to find the cause of the problem, call your dealer. DANGER: RISK OF ELECTROCUTION ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Make sure that the water volume in the too low installation is above the minimum required value (see "7.2.3 To check the water volume and flow rate" [ 57]). ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
If yes, make sure that the room where you want to purge air is sufficiently ventilated. Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
"7.2.4 Changing the pre-pressure of the expansion vessel" [ 59]). 13.3.6 Symptom: The pressure relief valve opens Possible causes Corrective action The expansion vessel is broken Replace the expansion vessel. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
▪ If the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your dealer. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
This chapter gives you an overview of all possible error codes and their descriptions as they appear on the user interface. For detailed troubleshooting of each error, see the service manual. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
OU: PCB defect. Power reset required. OU: Actuation of high pressure switch (HPS). Please contact your dealer. OU: Overheat of inverter compressor motor. Please contact your dealer. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 167
Please contact your dealer. OU: Abnormal high pressure in cooling. Please contact your dealer. OU: Abnormal high pressure, actuation of HPS. Please contact your dealer. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 168
Please contact your dealer. OU: Defect of power supply voltage. Please contact your dealer. OU: Transmission malfunction between main CPU- INV CPU. Please contact your dealer. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 169
Please contact your dealer. Leaving water temperature sensor problem. Please contact your dealer. Mixed water thermistor abnormality. Heat exchanger frozen. Heat exchanger frozen. Heat exchanger frozen. Heat exchanger frozen. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 170
Please contact your dealer. Flow sensor/switch malfunction. Please contact your dealer. Heat exchanger temperature sensor problem. Please contact your dealer. Room temperature sensor problem. Please contact your dealer. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 171
Please contact your dealer. Connection with room thermostat lost. No connection with room thermostat. Indoor unit, outdoor unit matching problem. Power reset required. Extension/hydro communication problem. Extension/hydro mismatch problem. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 172
If the problem persists, the unit will stop operation and the user interface will display error C0‑02. For the unit to resume operation, this error needs to be reset manually. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Installer settings > System operation > Pump down > Start pump down. 3 After ±2 minutes, close the liquid stop valve with a hexagonal wrench. 4 Check on the manifold if the vacuum is reached. ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 174
5 After ±5 minutes, close the gas stop valve, and stop the pump down operation by pressing on the user interface. Liquid stop valve Closing direction Hexagonal wrench Valve cap Gas stop valve ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Technical data 15 Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). In this chapter 15.1...
(3) Legend Live Neutral Protective earth Earth Field wiring Circuit breaker Connection Terminal strip Connector Terminal Black White Brown Green Yellow Orange Blue Grey Printed circuit board ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Ext. thermistor External thermistor Heat pump convector Heat pump convector Safety thermostat Safety thermostat Add LWT Additional leaving water temperature On/OFF thermostat (wired) On/OFF thermostat (wired) ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 180
Fuse T 5 A 250 V for PCB Contactor backup heater Safety contactor backup heater Relay 3-way valve bypass Relay 3-way valve flow K*R (A1P, A4P) Relay on PCB Additional zone pump ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 181
For preferential kWh rate power supply For preferential kWh rate power supply Indoor unit supplied from outdoor Indoor unit supplied from outdoor Normal kWh rate power supply Normal kWh rate power supply ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 183
Only for heat pump convector Only for heat pump convector Only for wired On/OFF thermostat Only for wired On/OFF thermostat Only for wireless On/OFF thermostat Only for wireless On/OFF thermostat ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Page 184
2 core 2x0.75 A13P: P1-P2 LAN adapter communication Only for EKRUDAL1 2 core (remote user interface) 2x0.75 A10 P: P1-P2 user interface communication 4D125238 2 core ERLA03DAV3 + EHFZ03S18DJ3V Installer reference guide Daikin Altherma 3 R F 4P596821-1 – 2019.10...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Page 186
ID9E51 Field settings table [6.8.2] = ..Applicable units EHFZ03S18DJ3V Notes — 4P596829-1 - 2019.10...
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value User settings └─ Preset values └─ Room temperature 7.4.1.1 Comfort (heating) [3-07]~[3-06], step: A.3.2.4 22°C 7.4.1.2 Eco (heating) [3-07]~[3-06], step: A.3.2.4 18°C 7.4.1.3 Comfort (*)
Page 188
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.3.1.1.1 LWT setpoint mode 0: Fixed 1: Weather dep. 2: Fixed / scheduled 3: WD / scheduled A.3.1.1.2.1 [9-01] Temperature range Minimum temp (heating) 15~37°C, step: 1°C...
Page 189
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value A.6.3.4 [5-09] kW value 0~20 kW, step: 0,5 kW 20 kW └─ Averaging time A.6.4 [1-0A] 0: No averaging 1: 12 hours 2: 24 hours 3: 48 hours...
Page 190
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [3-00] Is auto restart of the unit allowed? 0: No 1: Yes [3-01] [3-02] [3-03] [3-04] [3-05] [3-06] What is the maximum desired room temperature in heating? 18~30°C, step: 0,5°C 30°C [3-07]...
Page 191
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [8-02] Anti-recycling time. 0~10 hour, step: 0,5 hour 0,5 hour [8-03] [8-04] [8-05] Allow modulation of the LWT to control the room temp? 0: No 1: Yes [8-06]...
Page 192
Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Value Default value [D-09] Is an external kWh meter used for power measurement? 0: No 1: 0,1 pulse/kWh 2: 1 pulse/kWh 3: 10 pulse/kWh 4: 100 pulse/kWh 5: 1000 pulse/kWh [D-0A]...
Page 196