Daikin Altherma 3 R F Installer's Reference Manual page 134

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

9
|
Configuration
Installer reference guide
134
Do NOT use 1 or 3. Setting [D-00] to 1 or 3 when [D-01] is set to 1 or 2 will reset
[D-00] back to 0, as the system does not have a booster heater. Only set [D-00] to
the values in the table below:
[D‑00]
0 (default)
2
Power saving function
Defines whether the outdoor unit power supply can be interrupted (internally by
indoor unit control) during stand-still conditions (no space heating/cooling nor
domestic hot water demand). The final decision to allow power interruption of the
outdoor unit during standstill depends on the ambient temperature, compressor
conditions and minimum internal timers.
This setting is enabled by default and is read-only.
#
Code
N/A
[E-08]
Power consumption control
See
"5  Application guidelines" 
functionality:
#
[A.6.3.1]
[4-08]
[A.6.3.2]
[4-09]
[A.6.3.3]
[5-05]
[A.6.3.4]
[5-09]
Amp. limits for DI: Only applicable in case of power limitation mode based
on digital inputs and based on current values.
Backup heater
Forced OFF
Allowed
Power saving function for outdoor unit.
0: Disabled
1: Enabled (default)
4
[
  24] for detailed information about this
Code
Mode:
0 (No limitation)(default): Disabled.
1 (Continuous): Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 (Digital inputs): Enabled: You can set
up to four different power limitation values
(in A or kW) to which the system power
consumption will be limited when the
corresponding digital input asks.
Type:
0 (Current): The limitation values are set in
A.
1 (Power)(default): The limitation values are
set in kW.
Amp. value : Only applicable in case of full
time power limitation mode.
0 A~50 A, step 1 A
kW value : Only applicable in case of full time
power limitation mode.
0 kW~20 kW, step 0.5 kW
Compressor
Forced OFF
Description
Description
ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehfz03s18dj3vErla03dav3

Table of Contents