Daikin Altherma 3 R F Installer's Reference Manual page 135

Hide thumbs Also See for Altherma 3 R F:
Table of Contents

Advertisement

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
#
N/A
[5-05]
N/A
[5-06]
N/A
[5-07]
N/A
[5-08]
kW limits for DI: Only applicable in case of power limitation mode based on
digital inputs and based on power values.
N/A
[5-09]
N/A
[5-0A]
N/A
[5-0B]
N/A
[5-0C]
Average timer
The average timer corrects the influence of ambient temperature variations. The
weather-dependent set point calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
[A.6.4]
[1-0A]
Ext. amb. sensor offset.
ONLY applicable in case of an external outdoor ambient sensor is connected and
configured.
You can calibrate the external outdoor ambient temperature sensor. It is possible
to give an offset to the thermistor value. The setting can be used to compensate
for situations where the external outdoor ambient sensor cannot be installed on
the ideal installation location (see installation).
Code
Limit DI1
0 A~50 A, step 1 A
Limit DI2
0 A~50 A, step 1 A
Limit DI3
0 A~50 A, step 1 A
Limit DI4
0 A~50 A, step 1 A
Limit DI1
0 kW~20 kW, step 0.5 kW
Limit DI2
0 kW~20 kW, step 0.5 kW
Limit DI3
0 kW~20 kW, step 0.5 kW
Limit DI4
0 kW~20 kW, step 0.5 kW
Outdoor average timer:
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
9
Configuration
|
Description
Description
Installer reference guide
135