8.3.6 To connect the domestic hot water pump

ERLA03DAV3 + EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1 – 2019.10
INFORMATION
In case of an electricity meter with transistor output, check the polarity. The positive
polarity MUST be connected to X5M/6 and X5M/4; the negative polarity to X5M/5
and X5M/3.
1 Open the following (see
1 Top panel
2 Upper front panel
3 Upper switch box cover
2 Connect the electricity meters cable to the appropriate terminals as shown in
the illustration below.
A
B
A
B
3 Fix the cable with cable ties to the cable tie mountings.
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A
(continuous)
[A.2.2] Options > [A.2.2.A] DHW pump
[7.3] Set schedules > [7.3.7] DHW pump
1 Open the following (see
"6.2.4 To open the indoor
S3S
S2S
3
4
5
6
3 4 5 6
"6.2.4 To open the indoor
8
Electrical installation
|
4
unit" [
 44]):
X5M
4
unit" [
 44]):
Installer reference guide
1
3
2
89