Installation manual
Daikin Altherma 3 R F
https://daikintechnicaldatahub.eu
EBVZ16S18DJ6V
EBVZ16S23DJ6V
EBVZ16S18DJ9W
Installation manual
EBVZ16S23DJ9W
English
Daikin Altherma 3 R F

Advertisement

Table of Contents
loading

Summary of Contents for Daikin Altherma 3 R F

  • Page 1 Installation manual Daikin Altherma 3 R F https://daikintechnicaldatahub.eu EBVZ16S18DJ6V EBVZ16S23DJ6V EBVZ16S18DJ9W Installation manual EBVZ16S23DJ9W English Daikin Altherma 3 R F...
  • Page 2 3P655197-3A...
  • Page 3 3P655197-3A...
  • Page 4: Table Of Contents

    Configuration wizard: Main zone......... 31 ▪ Format: Paper (in the box of the indoor unit) + Digital files on http://www.daikineurope.com/support-and-manuals/product- 7.2.6 Configuration wizard: Additional zone......31 information/ 7.2.7 Configuration wizard: Tank ......... 32 Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 5: Specific Installer Safety Instructions

    Daikin website (publicly accessible). recommended by the manufacturer. ▪ The full set of latest technical data is available on the Daikin ▪ Be aware that R32 refrigerant does NOT contain an Business Portal (authentication required).
  • Page 6: About The Box

    About the box Indoor unit ▪ At delivery, the unit MUST be checked for damage. Any damage MUST be reported immediately to the claims agent of the carrier. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 7: Unit Installation

    ▪ Domestic hot water production: 5~35°C WARNING INFORMATION Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable Cooling is only applicable in case a conversion kit (EKHVCONV*) is installed. legislation and are executed ONLY by authorised persons.
  • Page 8: Installation Patterns

    =1.86 m + Chimney height release Installation with chimney connected to the outside. The release height is not relevant. There are no requirements to the minimum floor area. Not applicable Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 9 ▪ Must be a permanent opening that cannot be closed. ▪ Must be ≥50% of A (minimum bottom opening area). nv-min Min. 50% ▪ Must be ≥1.5 m from the floor. of A nv-min (≥A nv-min EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 10 Ventilation openings must comply with A and with nv-min "Conditions ventilation openings" on previous page). Min. 50% Min. 50% ΔH1 of A of A nv-min nv-min (≥A (≥A nv-min nv-min Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 11 35.00 3.30 2.10 1.72 3.47 2.21 1.81 3.91 2.49 2.03 1.76 4.34 2.77 2.26 1.96 1.75 4.78 3.04 2.49 2.15 1.93 1.76 5.04 3.21 2.62 2.27 2.03 1.85 1.72 EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 12 Floor area of room A (m²) [! NOT room A + room B !] 5.00 10.00 15.00 20.00 25.00 30.00 35.00 1.66 1.86 2.06 2.26 2.46 2.66 2.86 3.06 Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 13: Opening And Closing The Unit

    4.3 kg, use the row of 4.4 kg. Total refrigerant charge (kg) (dm²) nv-min X 1 A 10.1 10.4 X 1 4 Y 10.6 10.9 11.1 11.3 11.5 3 Remove the switch box cover. 11.8 EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 14: To Lower The Switch Box On The Indoor Unit

    During the installation, you will need access to the inside of the irregularities. The maximum allowed deviation is 1°. indoor unit. To have easier front access, put the switch box lower on the unit as follows: Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 15: To Connect The Drain Hose To The Drain

    ▪ with a heat resistance of at least 120°C ▪ Insulation thickness Pipe outer diameter Insulation inner Insulation thickness (Ø diameter (Ø 9.5 mm (3/8") 12~15 mm ≥13 mm 15.9 mm (5/8") 17~20 mm ≥13 mm EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 16: Connecting Refrigerant Piping

    See the recommended procedure as described in "8.2  Checklist temperatures: commissioning" [ 4  37]. during INFORMATION The following illustration is an example and might NOT match your system layout. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 17: Connecting Water Piping

    It is recommended to install shut-off valves to domestic cold water in and domestic hot water out connections. These shut-off valves are field supplied. 4 Reattach the top panel. EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 18: To Fill The Water Circuit

    ▪ [3.9] (read-only) Control a Refrigerant gas pipe About electrical compliance Only for the backup heater of the indoor unit supply" [ 4  20]. "6.3.2 To connect the backup heater power Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 19: To Connect The Main Power Supply

    [1.6] Room sensor offset (field supply, see addendum book for optional equipment) 6.3.1 To connect the main power supply unit" [ 4  13]): 1 Open the following (see "4.2.1 To open the indoor EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 20: To Connect The Backup Heater Power Supply

    3~ 230 V (6T1) 3+GND contact shall ensure the minimum applicable load of 15 V DC, 10 mA. 3N~ 400 V 4+GND [9.8] Benefit kWh power supply [9.3] Backup heater Connect X11Y to X11YB. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 21 Overcurrent fuse (field supply). Recommended fuse: 4‑pole; 20 A; curve 400 V; tripping class C. Safety contactor (in the lower switch box) Q1DI Earth leakage circuit breaker (field supply) Switch box Terminal (field supply) EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 22: To Connect The Shut-Off Valve

    [9.2.2] DHW pump [9.2.3] DHW pump schedule unit" [ 4  13]): 1 Open the following (see "4.2.1 To open the indoor 3 Fix the cable with cable ties to the cable tie mountings. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 23: To Connect The Alarm Output

    2 Connect the space cooling/heating ON/OFF output cable to the Wires connected to the alarm appropriate terminals as shown in the illustration below. output Wire between X2M and A4P A4P Installation of EKRP1HBAA is required. EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 24: To Connect The Power Consumption Digital Inputs

    1 Top panel 2 User interface panel 3 Upper switch box cover 2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 25: To Connect A Smart Grid

    Note: The jumper wire (factory-mounted) must be removed from the Grid modes: respective terminals. Smart Grid contact Smart Grid operation mode Free running Forced off Recommended on Forced on EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 26 Screws for K1A and K2A Sticker to put on the high voltage wires Wires between the relays and X5M (AWG22 ORG) Wires between the relays and X10M (AWG18 RED) Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 27: To Install The Mounting Plate

    This chapter describes what you have to do and know to configure the system after it is installed. High voltage Smart Grid contact 1 High voltage Smart Grid contact 2 EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 28: To Access The Most Used Commands

    — level. ▪ Browse through the list of digits and change the selected digit. ▪ Move the cursor from left to right. ▪ Confirm the pin code and proceed. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 29: Configuration Wizard

    The system can supply leaving water to up to 2 water temperature Code Description zones. During configuration, the number of water zones must be set. [9.3.1] [E‑03] ▪ 3: 6V ▪ 4: 9W EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 30: Configuration Wizard: Backup Heater

    Only for systems with integrated domestic hot water tank: If the storage temperature setpoint is higher than 50°C, Daikin recommends NOT to disable the backup heater 7.2.4 Configuration wizard: Backup heater second step because it will have a big impact on the...
  • Page 31: Configuration Wizard: Main Zone

    [2.C]. Emitter type Control For more info about this functionality, see "7.2.5  Configuration zone" [ 4  31]. wizard: Main Define how the operation of the unit is controlled. EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 32: Configuration Wizard: Tank

    Because the slope of the curve depends on local circumstances such as climate and the insulation of the house, the curve can be adjusted by an installer or user. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 33: 2-Points Curve

    : Domestic hot water Possible actions on this screen X1, X2 Examples of outdoor ambient temperature Go through the temperatures. Change the temperature. Go to the next temperature. Confirm changes and proceed. EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 34: Using Weather-Dependent Curves

    [2.6] Main zone > Cooling WD curve ▪ [C‑07]=2 (Room thermostat) Additional zone – Heating [3.5] Additional zone > Heating WD curve Additional zone – Cooling [3.6] Additional zone > Cooling WD curve Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 35: Additional Zone

    ▪ 2: 2 contacts 7.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 36: Menu Structure: Overview Installer Settings

    Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 37: Commissioning

    Next commissioning instructions in this chapter, a general ▪ Between the local supply panel and the indoor unit commissioning checklist is also available on the Daikin ▪ Between the indoor unit and the valves (if applicable) Business Portal (authentication required).
  • Page 38: To Check The Minimum Flow Rate

    2 Select OK to confirm. 8.2.4 To perform an actuator test run Conditions: Make sure all operation is disabled. Go to [C]: Operation and turn off Space heating/cooling and Tank operation. Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 39: To Perform An Underfloor Heating Screed Dryout

    12 hours of power-on, manually disable room frost protection by setting [2‑06] to "0", and KEEP it disabled until the screed dryout has finished. Ignoring this notice will result in cracking of the screed. EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 40: 10 Technical Data

    10 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 10.1 Piping diagram: Indoor unit...
  • Page 41: Wiring Diagram: Indoor Unit

     WLAN cartridge  WLAN cartridge Relay 3-way valve bypass Main LWT Main leaving water temperature Relay 3-way valve flow  On/OFF thermostat (wired)  ON/OFF thermostat (wired) K*R (A4P) Relay on PCB EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 42 WLAN cartridge WLAN cartridge Only for wireless On/OFF Only for wireless ON/OFF (5) Ext. thermistor (5) External thermistor thermostat thermostat Switch box (6) Field supplied options (6) Field supplied options Installation manual EBVZ16S18+23DJ Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 43 & add: X2M: 3-4 signal 2 core Power limitation demand input 4 A8P: X801M: 4-5 signal Only for Human Comfort Interface 2 core 2×0.75 X5M: 11-12 A14P: P1-P2 user interface communication 4D128800 EBVZ16S18+23DJ Installation manual Daikin Altherma 3 R F 4P643601-1B – 2021.10...
  • Page 44 4P643601-1 B 0000000Y 4P643601-1B 2021.10 Verantwortung für Energie und Umwelt...