VAV Zone II Secondary Duct specifications

Power requirements
Actuator
Act Net port
Protection
Status indicators
Environmental operating
range
Integral airflow sensor
Controller and actuator
overall dimensions
Controller and actuator
mounting dimensions
Controller overall
dimensions
Controller mounting
dimensions
Actuator overall dimensions
Actuator mounting
Weight
Listed by

Safety considerations

WARNING Disconnect electrical power to the Zone Ctrl II before wiring it. Failure to follow this warning could
cause electrical shock, personal injury, or damage to the controller.
Zone Ctrl II and
VAV Zone II Secondary Duct Installation and Start-up Guide
Error! No text of specified style in document.
The VAV Zone II Secondary Duct receives power from the Zone Ctrl II. Increase the
controller's power supply by 3 VA when connecting a VAV Zone II Secondary Duct.
Belimo brushless DC motor, torque 45 inch-pounds (5 Nm), runtime 154 seconds
To connect the actuator to the VAV Zone II Secondary Duct controller and to the
Zone Ctrl II
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
LEDs indicate status of communications, running, power, and motor direction
32 to 130°F (0 to 54.4°C), 10–90% relative humidity, non-condensing
Precision differential pressure sensor 0–2 in. H2O, sensitive down to ±0.001 in.
H2O. Barbed tapered airflow connections accept 3/16 in. (4.75 mm) I.D. tubing.
Allows for readings across the 0–2 in. H2O range, accurate to ±5% of full flow at 2
in. H2O.
Width:
8.9 in. (22.7 cm)
Height:
5.9 in. (15.0 cm)
7.1 in. (18.0 cm) from left side controller mounting hole centerline to actuator
mounting hole centerline
Width:
6.4 in. (16.3 cm)
Height:
5.7 in. (14.5 cm)
Depth:
2.1 in. (5.3 cm)
5.3 in. (13.4 cm) from left side controller mounting hole centerline to right side
controller mounting hole centerline
Width:
3.0 in. (7.6 cm)
Height:
5.9 in. (15.0 cm)
Depth:
2.5 in. (6.4 cm)
4.4 in. (11.2 cm) from shaft centerline to mounting hole centerline
1.8 lbs (0.82 kg)
UL-916 (PAZX), cUL-916 (PAZX7), FCC Part 15-Subpart B, Class B, CE