Charger Mode Specifications; General Specification - PROLiNK PRO2000LD User Manual

Outdoor line interactive ups (1p/1p) - rack 2kva
Table of Contents

Advertisement

6.3 Charger Mode Specifications

Appropriate battery type
Charging Current
Max charger current limitation
Charging Algorithm
Charger voltage Setting @25 °C
Battery Temperature Control

6.4 General Specification

Dimension, W*D*H (mm)
Net Weight (Kgs)
Operation Temperature Range
Storage Temperature Range
Relative humidity
Audible Noise
Cooling
EMI
Surge protection
2Amp/ 4Amp/ 6Amp/ 8Amp/10Amp adjustable
Charger
Current(A)
10
8
Battery Type
AGM
Charging voltage is compensated according to battery temperature
-2.5mV /-3.0mV/ -3.5mV/ -4.0mV per cell per°C compensated coefficient
Charger on when battery temperature between - 20 °C to 50 °C
-40°C ~ 80°C for 120Vac model;
-40°C ~ 70°C for 230/240Vac model
Class A FCC/CISPR [EN50091-2: 1995]
IEEE/ANSI C.62.41 & 2KV, L-N
31
AGM
Temperature
40
50
3-Step
Boost CC, CV
24/48Vdc
28.2/56.4Vdc
adjustable
400*240*133
13kg
-50°C ~ 80°C
5% ~ 95% non-condensing
< 48dB
Forced Air
(
)
°C
Float
24/48Vdc
27.0/ 54.0Vdc

Advertisement