Special Jack Error Codes on OneControl
Touch Panel or OneControl App
To clear the error codes listed below:
1. Correct or otherwise repair the issue.
See the table below.
2. To clear the special jack error code, the jacks need to
be "homed." To "home" jacks, each jack must be able to
retract a minimum of 6".
3. The Power Tongue Jack does not need to be "homed."
The Power Tongue Jack cannot be operated from the
OneControl Touch Panel or OneControl App while clearing
the special jack error codes. The Power Tongue Jack
can be operated using the RET/EXT switch (Fig.42) on the
tongue jack during this procedure.
4. Extend all jacks to reach the 6" of minimum
retract needed.
Touch Panel Message
Touch Panel Message
***ERROR***
Left-Front Jack Fault
Right-Front Jack Fault
Left-Rear Jack Fault
Right-Rear Jack Fault
Tongue Jack Fault
lci1.com
Why?
Why?
Error at a specific jack (left front,
right front, left rear, right rear,
tongue). Hall signal issue (open,
short, malfunction or loss of
communication); open or short
circuit between controller and motor.
574-537-8900
Ground Control
Leveling OneControl
Touch Panel
Installation and Owner's Manual
(For Aftermarket Applications)
A. Press EXTEND and FRONT buttons to extend the front
jacks, if required. See OneControl Touch Panel Operation
or OneControl App Operation section.
B. Press EXTEND and REAR buttons to extend the rear
jacks, if required. Refer to Operation - OneControl Touch
Panel and Operation - OneControl App sections.
5. Press ENTER button to begin auto retracting the jacks.
The jacks will retract until they reach the hard current
limit. The Power Tongue Jack will perform an automatic
grounding during the auto retracting sequence.
6. The jacks are now "homed" and the special jack error
code will be cleared.
NOTE: If the jacks do not retract, an error should display
on the touch panel screen. This is typically caused by
wiring interruption.
What should be done?
What should be done?
Check voltage at the battery under load.
Check harness connections at controller and at jack.
Check harness for damage.
Check fuses at controller.
Repair or replace as necessary.