14.1.2

Device Inspections upon Receipt

14.1.2.1 Check of the Rated Data

First of all, check the complete ordering code (MLFB) and the delivery note to ensure that the
version delivered complies with the required rated data and functions, and that the necessary
and desired accessories are complete.

14.1.2.2 Electrical Check

Please observe the operating conditions according to VDE0100 and VDE0105 part 1.
The device must be in the final operating area for a minimum of two hours before the power
source is first applied. This time allows the device to attain temperature equilibrium, and
dampness and condensation are avoided.
WARNING
Warning about dangerous voltages.
Nonobservance of the safety instructions means that death, heavy
injuries or considerable material damages can occur.
Electric checks may be performed only by qualified personnel who are familiar with and
adhering to safety requirements and precautionary measures, may perform these steps.
For a first electrical check of the device, it is sufficient to ensure reliable earthing and to connect
the auxiliary supply voltage:
Connect the earthing electrode of the device to the protective earthing. The earthing screws
are positioned at the rear panel in the case of cubicle mounting and panel flush mounting. In
the case of surface mounting, an earthing terminal is used.
Wire the supply voltage to the device inputs observing the correct height and polarity of the
supply voltage (see chapter 16.1).
Switch the device on using the mains switch.
All LEDs at the front of the device are active during booting. After approx. ten seconds, all
LEDs are extinguished. If a battery package has been installed, the battery test is started with
the Accumulator capacity OK LED blinking, which is complete after 30 seconds. The
device is ready for operation, as soon as the Device ready for operation, Operating
voltage OK and the Normal mode LEDs light up. If the Accumulator capacity OK LED is
blinking, the battery package is being charged.
14.1.3

Operation with OSCOP P

You can operate the digital fault recorder SIMEAS R-PMU using the system software OSCOP P.
For detailed information, please refer to the Chapter 12.
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
14
14.1 Getting Started
185