14.1 Getting Started

14.1 Getting Started
This chapter describes the first steps that you should take after receiving your SIMEAS R-PMU.
After unpacking, please check whether the design and rated data of the device match your
requirements.
For an electrical check, you can now navigate in the user interface without any measured values
for the first time. Furthermore, you can connect the device to a notebook or a personal computer
and operate it using OSCOP P.
In the last section you will find hints on what to observe for the long-term transport and storage
of the system.
14.1.1

Unpacking and Repacking the Device

The devices are packed appropriately at the factory for transport. Unpacking and repacking must
be performed with the usual care, without force and only with the aid of suitable tools. Visually
check the device immediately upon arrival for correct mechanical condition.
Please observe further notes that may have been attached.
The shipping packaging can be reused in the same manner for further shipment. The storage
packaging of individual devices is not sufficient for shipping.
If other packaging is used, it must be ensured that the transport requirements are met.
The device must be in the final operating area for a minimum of two hours before the power
source is first applied. This time allows the device to attain temperature equilibrium, and
dampness and condensation are avoided.
184
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012