Local Printer

The local printer is used for the automatic, graphical output of TAR records. The printer provides
the operating personnel with an overview of the cause of the fault record. The printout can be
used for a first analysis of the fault event and also for documentation purposes.
Even after it has been printed, all measured data remains in the memory as a fault record. This
can be called up with the OSCOP P analysis program at a later point in time.
Apart from the header data (device name and location), the printout contains the following
information:
a channel legend,
the trigger cause,
the trigger time stamp and
the analog and binary channels.
The printout of a fault record comprises a maximum of 5 seconds of the parameterized recording
time.
Note
The time axis of the printout shows generally the UTC time stamp, irrespectively of the parame-
terized time zone.
Note
The printer must be equipped with the maximum possible memory, in order to ensure trouble-
free functioning. The minimum memory size is 32 Mbyte.
Enabled printers
For a list with the printers recommended for connection, please refer to the Internet URL
www.simeas.com. This list is regularly updated
Printer connection (parallel port)
The parallel interface PRINTER (LPT 1) is provided for the connection of a printer.
Connection method
25-pin standard D-SUB plugs can be used as connectors.
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
.
11
129