13
13.2 Operator and Error Messages
Table 13-2 shows the allocation of LEDs 9 to 21 at delivery and describes the meaning of the
individual operator messages.
Table 13-2
Operator messages via LEDs
LED no.
9
Device ready for operation
10
Supply voltage OK
11
Battery buffer OK
12
Recording active
13
Device synchronized
14
Communication active
15
Ring buffer active
16
PMU active
17
Group alarm
18
Normal mode
19
Lock mode
20
Test mode
21
Manual triggers
178
Message
Definition
Device is ready for operation, no malfunctions
Supply voltage is present
Battery buffer operating without malfunctions
(optional)
Is lit for the duration of a triggered fault recording
(TAR or TPR) - not with trigger cause "external
start"
LED flashes: a valid synchronization signal has
been detected, however, the device is not
synchronized yet;
LED lights up:device is synchronized
A communication has been set up by OSCOP P
Records are deleted because ≥90 % of the
reserved memory space has been reached
LED flashes: PMU recording is active, however,
no PMU data is transferred to the PDC;
LED lights up: PMU recording is active and PMU
data is transferred to the PDC
Device has malfunctioned
Device is in normal mode, all triggers are active
Device is in lock mode, all triggers are deactivated
Device is in test mode, all triggers are active;
"Test" is entered as trigger cause
Manual triggering of a record; "Manual" is entered
as trigger cause
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012