Error Messages - Siemens SIMEAS R-PMU Manual

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

A.2

Error Messages

OSCOP P displays the following error messages if the communication to SIMEAS R-PMU is
active:
Message ID
800
Unknown command received
801
Incorrect password or command not
executable
802
Command not executed
803
Command executed with error status
804
Illegal or invalid command parameter
805
Command executed on inactive
recorder
807, 810 -
File access error
812
808
Directory access error
814
Database query outside time range
815
Database transmission overwritten
by measure
818
Error during compilation of system
parameters
819
Error during compilation of DAU
parameters
820
Error during parameterization, file
does not contain system data
821
Parameterization error, slot not
occupied
822
Parameter file update error
823
Error during firmware update
824
Error setting system information
825
Data transmission canceled
830
Time setting via the PC interface is
not allowed with synchronization type
GPS
831
Time setting via the PC interface can
be performed only every 4 hours
832
V2/V3 command rejected
833
Incorrect password
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Error/Message
Comment
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Unable to execute command: Recorder not active or
parameterized.
Query table of contents again and check if the record has
been deleted via ring buffer mode, contact hotline if
necessary
Contact hotline
There are no records/entries for the given interval.
The requested record of a continuous recorder was
overwritten in ring buffer mode.
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
Check the communication link, contact hotline if
necessary
Firmware or OSCOP update recommended, contact
hotline if necessary
-
Time setting via the PC interface is not allowed with
synchronization type GPS/DCF77.
Set a cycle time of at least 4 hours for automatic time
setting.
You tried to access the SIMEAS R-PMU with device type
SIMEAS R. Create a device in OSCOP P Parameterize
PC with device type SIMEAS R-PMU. This device type is
available in OSCOP P 6.60.
Parameterize the correct password, refer to chapter
12.1. In general, the password may be overwritten in the
first 3 minutes after new start of the device.
2 Error Messages
279

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents