Siemens SIMEAS R-PMU Manual page 281

Digital fault recorder
Hide thumbs Also See for SIMEAS R-PMU:
Table of Contents

Advertisement

Log No. Type
Class
291
2
SYSTEM
292
2
SYSTEM
293
2
SYSTEM
294
2
SYSTEM
295
2
SYSTEM
296
2
SYSTEM
297
2
SYSTEM
298
2
SYSTEM
299
2
SYSTEM
300
0
SYSTEM
384
0
BOOT
386
1
BOOT
387
0
BOOT
388
1
BOOT
389
0
BOOT
390
0
BOOT
393
0
BOOT
395
2
BOOT
396
2
BOOT
397
2
BOOT
398
2
BOOT
399
2
BOOT
400
0
BOOT
401
1
BOOT
402
1
BOOT
403
1
BOOT
404
1
BOOT
405
1
BOOT
406
1
BOOT
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
Description
Restart cause: File system cannot be
initialized
Restart cause: Log recorder cannot be
initialized. Time stamp:
Restart cause: Folder tree structure cannot
be initialized. Time stamp:
Restart cause: Battery fault.
Time stamp:
Restart cause: Fault in log recorder queue.
Time stamp:
Restart cause: Log recorder cannot be
opened. Time stamp:
Restart cause: Invalid log recorder format.
Time stamp:
Critical system fault: Task suspended.
Task no.:
Critical system fault: Recorder task
suspended. Task no.:
Self-monitoring: DAU fault
Mismatch fault: DAU found but not
configured
Fault: DAU configured but not plugged in
Fault booting the DAU
Mismatch fault: Incorrect DAU configured
Fault configuring the DAU
Fault setting the DAU time
Fault starting DAU
DAU type slot 1
DAU type slot 2
DAU type slot 3
DAU type slot 4
Device booting with firmware version:
Fault booting the communication processor.
Internal fault number:
DAU deactivated
Initialization finished
DAU calibration frequency 16.66 Hz, type
not supported
Wrong DAU calibration frequency of 50 Hz
for 60 Hz system
Wrong DAU calibration frequency of 60 Hz
for 50 Hz system
Unknown DAU calibration frequency
3 System Messages
Comment
Flash disk fault; Hotline
Flash disk fault; Hotline
Flash disk fault; Hotline
Replace battery pack
Hotline
Hotline
Hotline
Hotline
Hotline
DAU hardware/software fault; Hotline
All plugged in DAUs must be
parameterized. DAUs not needed can be
deactivated.
Parameterized DAUs must be plugged in
Hotline
Wrong DAU type parameterized
Several possible reasons: DAU and CPU
software version do not match, firmware
update recommended; DAU hardware error;
contact hotline if necessary
Hotline
Hotline, DAU hardware error
-
-
-
-
-
Hotline, CPU or DAU hardware fault
-
Possibly an error message after an
upgrade; otherwise hotline
(consider additional texts)
SIMEAS R-PMU supports 50 Hz and 60 Hz
DAU types only.
Nevertheless, the device is ready for work
generating wrong measured values.
Only 60 Hz DAU types are allowed for
60 Hz nominal frequency.
Nevertheless, the device is ready for work
generating wrong measured values.
Only 50 Hz DAU types are allowed for
50 Hz nominal frequency.
Nevertheless, the device is ready for work
generating wrong measured values.
Hotline, DAU hardware fault
281