16.1 Technical Data of the SIMEAS R-PMU
16.1.3

Phasor Measurement Unit (PMU)

General data
Protocol
Total vector error (TVE)
Compliance level
Data transfer rate (reporting rate)
Communication:
Ethernet settings
RS232 settings
244
IEEE C37.118-2005
1 %
1
10, 25, 50 messages/s with f
10, 12, 15, 20, 30, 60 messages/s with f
TCP and UDP via LAN (Ethernet),
PPP via RS232 (modem, null modem)
Ports freely parameterizable
default setting 4712/TCP or 4713/UDP
PPP network protocol
TCP transport protocol
Port freely parameterizable, default setting 4712/TCP
Modem / null modem 115,200 bit/s fix
CHAP authentification (user: simeasr, the password is
the same as the SIMEAS R-PMU password, see
chapter 4.7.2 in the OSCOP P manual)
No data coding
No data compression
LCP extensions
Van Jacobson TCP/IP header compression
IP address auto negotiation or fixed IP address
allocation
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012
= 50 Hz
n
= 60 Hz
n