10.3 COM S - Maintenance Interface (Service Interface)

10.3
COM S - Maintenance Interface (Service Interface)
The serial interface COM S at the front side is the interface for parameterization. But it can also
be used for the transfer of measured data. A PDC cannot be connected to the service interface
of the SIMEAS R-PMU.
The interface parameters have been set as follows and cannot be changed:
Baud rate:
Data bits:
Stop bit:
Parity:
Hardware-Handshake:
SIMEAS R-PMU
COM S
Service interface
Front panel
Null modem cable, SIMEAS R-PMU -
evaluation PC or DAKON
Figure 10-6 Serial data transmission (service interface)
124
19,200 bit/s
8
1
none
not supported
Note
The maintenance interface supports only the null modem connection to
OSCOP P. Modem, X.25 and star coupler connections and connections to PDCs
are not supported.
SIMEAS R-PMU
COM 1 Datenschnittstelle
Rückseite
Evaluation PC
DAKON
Digital Fault Recorder, SIMEAS R-PMU, Manual