14
14.3 Extending the Existing Hardware
16. Connect the measuring signals to the new adapters.
17. Apply the supply voltage to the device.
18. Switch the device on using switch S1.
19. Connect a notebook to the service interface COM S at the front of the device for
parameterization.
20. Enable the new module using the OSCOP P system program and set the parameters for the
individual channels. For detailed information regarding the parameterization, please refer to
Chapter 12.
Figure 14-2 View of the adapters
200
Digital Fault Recorder, SIMEAS R-PMU, Manual
E50417-H1076-C360-A5, Release 10.2012