Gree U-MATCH Series Service Manual page 99

Dc inverter air conditioners
Hide thumbs Also See for U-MATCH Series:
Table of Contents

Advertisement

U-Match Series DC Inverter Service Manual
NO.
SILK-SCREEN
1
AC-L
2
AC-N
3
PWR 1
4
DC_MOTOR2
5
DC_MOTOR1
6
CN3
7
COMM1
8
CN2
9
CN1
10
H-PRESS
11
HPP
12
LPP
13
OVC-COMP
14
T-SENSOR2
15
FA
16
HEAT
17
VA-1
18
4V
INTERFACE
Live wire input
Neutral wire input
Control
power
output[1-
voltage,3- GND]
DC fan motor2
1-pin: Power supply of fan motor
3-pin: Fan GND
4-pin: +15V
5-pin: Signal control
6-pin: NC
DC fan motor1
1-pin: Power supply of fan motor
3-pin: Fan GND
4-pin: +15V
5-pin: Signal control
6-pin: Signal Feedback
Control power output[1-GND、2-18V、
3-15V]
Communication line [1-3.3V 、 2-TX 、
3-RX、4-GND]
Communication line with1-pin GND,
2-pin B and 3-pinA)
Communication line with 1-pin plus
12V, 2-pin B, 3-pin A and 4-pin GND
High pressure switch for fan speed
adjustment
High
pressure
switch
protection (obligate)
Low
pressure
switch
protection (obligate)
Compressor overload protection
1&2 pin: Tube sensor
3&4 pin: Ambient temperature
5&6 pin: Air discharge
Electronic expansion valve line
1 to 4-pin: Drive impulse output;5-pin:
+12V;
Compressor electrical heater
Chassis electrical heater
4-way valve
96
INTERFACE INSTRUCTION
Live wire input
Neutral wire input
Power supply interface to the
DC
bus
drive
1-pin: DC bus voltage
3-pin: DC bus GND
Interface of DC fan motor
1-pin: DC bus voltage
2-pin: Suspended
3-pin: DC bus GND
4-pin: +15V
5-pin: Control signal input
6-pin: Not connected
Interface of DC fan motor
1-pin: DC bus voltage
2-pin: Suspended
3-pin: DC bus GND
4-pin: +15V
5-pin: Control signal input
65-pin: DC fan motor feedback
Power supply interface to the
drive
1-pin: GND
2-pin: +18V
3-pin: +15V
Communication needle stand of
main control drive
1-pin: +3.3V, 2-pin: TXD
3-pin: RXD, 4-pin: GND
Communication
with indoor unit
1-pin: GND, 2-pin: B,
3-pin: A
Communication
(reserved):
1-pin: +12V, 2-pin: B,
3-pin: A, 4-pin: GND
Pressure protection switch for
fan speed adjustment
for
system
Interface
protection
for
system
Interface
protection
Interface of compressor overload
protection
1&2
pin:
sensor
3&4 pin: Ambient temperature
sensor
5&6 pin: Discharge temperature
sensor
Interface of electronic expansion
valve:
1 to 4-pin: Drive impulse output;
5-pin: +12V;
Compressor electric heating belt
Chassis electric heating belt
4-way valve
needle
stand
interface
of
high
pressure
of
low
pressure
Case
temperature