Installation; Indoor Unit Installation; Installation Of Duct Type - Gree U-MATCH Series Service Manual

Dc inverter air conditioners
Hide thumbs Also See for U-MATCH Series:
Table of Contents

Advertisement

INSTALLATION

1 INDOOR UNIT INSTALLATION

1.1 Installation of Duct Type

1.1.1 Before Installation
After receiving the machine, please check for any transport damage. If finding any surface or
internal damage, please immediately report to the transport company or equipment company in writing.
After receiving the machine, please check the unit and accessories in reference to the packing list.
Ensure that the model is correct and the machine is in good condition. Please also check if the
specification and quantity of accessory parts are correct.
Determine the correct handling route and methods, thus to avoid damaging the unit or causing
possible hazard. For the sake of protection and safety, it is suggested to move the unit with the
packaging box. Even though it is not permitted to do like this under special occasions, do not remove the
packaging box, thus to avoid loosening or falling during handling.
Confirm if the installing foundation is solid. When this unit is to be installed on the metal section of
the building, make sure that the electrical insulation must comply with applicable standards.
Ensure that the place of installation is far from the area where the inflammable or explosive
substances are stored, thus to avoid possible explosion or fire due to leakage.
1.1.2 Installation Site
Ensure the top hanging piece has strong strength to withstand the weight of the unit.
The drainage pipe has convenient flow of water.
There is no obstacle blocking the return air inlet and exhaust outlet, so as to ensure sound air
circulation.
The installation spaces required by the drawing must be ensured, so as to provide enough space for
the service and maintenance.
The installation site must be far away from heat source, leakage of inflammable gas or smoke.
The indoor unit is of ceiling mount (indoor unit is hidden inside the ceiling).
The indoor and outdoor units, the power cable and the connecting electrical lines must be at least 1
meter from any TV set or radio. This is to avoid image interference or noise of the TV set or radio. (Even
if the distance is 1 meter, noise can also exist if there is strong electric wave.)
1.1.3 Caution for Installation
Generally, the unit is installed indoor on ceiling. For ceiling mounting, ensure that the hangers on
ceiling have adequate strength to support the weight of the unit.
To meet the noise and vibration requirements, the unit shall be installed by using rubber pad
(thickness ≥20mm) and rubber connector.
Insert a M10 expansion bolt into the hole. Drive a nail into the bolt. Refer to the profile dimensions
drawing of the indoor unit for the distance between the holes. Refer to Figure 3-1-1 for the installation of
the expansion bolt.
U-Match Series DC Inverter Service Manual
51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents