Gree U-MATCH Series Service Manual page 40

Dc inverter air conditioners
Hide thumbs Also See for U-MATCH Series:
Table of Contents

Advertisement

No.
Terminal name
1
CN1
2
X1(AC-L, AC-N)
3
X2
(2) Function instructions:
In order to achieve this function, set it through wired controller and refer to the following operation
method. It is defaulted that this function is not activated; if this function is set and door control
accessories are connected, the unit will control the ON/OFF of unit according to the card state detected
by door control detection board. When the card is not connected, the unit will turn to standby state. If the
unit is with wired controller,
If the unit is without wired controller, there will be no display. The unit will control the ON/OFF of unit
according to the detected information.
(3) Setting method:
Under off state of the unit, press Function and Timer buttons at the same time for 5s to go to the
debugging menu. Press Mode button to adjust to "08" in temperature displaying zone. Timer zone
displays setting state and press ▲ or ▼ button to adjust. There are 2 selections:
1) Without door control function (LCD displays 00)
2) With door control function (LCD displays 01)
Choose the second selection and then press Enter/Cancel button to save and exit setting. Now,
door control function is activated. The unit will memorize this setting status. The setting value will be
memorized after power failure. The detailed setting is as shown in the Figure below:
Table 2-7-3 Door control wiring port
CN1 wiring terminal and door control interface of indoor mainboard
X1(AC-L, AC-N) wiring terminal, connected to door control input
signal, rated voltage 220V.
X2 wiring terminal, connected to door control input signal
icon will be displayed on the wired controller.
37
U-Match Series DC Inverter Service Manual
Terminal instruction