System Capacity And Expandability

6 S
C
YSTEM
6.1 B
S
ASE
YSTEM
Item
Communications Ring
8 System Outputs
Power Supply
2 Local AZF's
2 RS232 communication
ports
Keyboard Interface
System Memory
6.2 E
XPANSION
Item
Loop Interface Module
(LIM)
Network Interface
Module (NIM)
Panel Expansion Relays
(IFS-717)
BC-200 Manual – P/N DOC-01-013
A
APACITY
ND
Description
RS485 communications ring to support
Up to 100 Field Modules
Up to 50 Annunciators
4 x Monitored Outputs.
4 x Clean contact relays
2.6 A power supply and battery
charger
Fused 27.3Vdc outputs
AZF 1
AZF 2
Laptop interface
System event printer
Remote terminal mode
PS2 QWERTY IBM PC keyboard
Approx. 4300 Named points
Approx. 4000 Control scripts
4000 History events
PCB
S
Description
Interface module to communicate with
up to 5 x pairs of LCM/LEM modules.
I.e. total of 4 CLIP Analog addressable
loops
Interface module to communicate with
the Network Control Module (NCM)
Relay card with 8 relays – contact
rating is 1A @ 24Vdc
E
XPANDABILITY
Bell Output
3 Additional
programmable outputs
General Alarm Output
General Fault Output
2 x programmable outputs
Notes
Fault output is normally
energised using V5.00
and above firmware.
Max contact rating of all
relays 1A @ 30Vdc.
A larger power supply
may be required if total
module load exceeds
2A. Power supplies up
to 11.7A are available.
Notes
Each Analog
addressable loop
supports up to 99
detectors and 99
addressable modules
using the CLIP protocol
Up to 8 IFS-717 8-way
relay boards can be
added
17