MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM

System Overview

Overview of Hardware

Feature
NTC10kΩ (Type II) / NTC20kΩ (Type II) /
0...10V / slow BI, 0.4 Hz
UI
NTC10kΩ (Type II) / NTC20kΩ (Type II) /
0...10V fix pull-up / slow BI, 0.4 Hz
Open = 24 V / closed 2.0 mA / totalizer 15
BI
Hz
AO
0..11 V (max. 1 mA)
Relay N.O. contact: 3 A, 250 VAC, 30 VDC
Relay N.O. contact (high in-rush): 10 A,
BO
250 VAC, 30 VDC
Relay N.O. contact with one common: 3 A,
250 VAC, 30 VDC
Total I/Os
RS485-1, isolated, BACnet MS/TP, Panel
Bus, or Modbus RTU Master or Slave
communication
RS485-2, non-isolated, BACnet MS/TP,
Panel Bus, or Modbus RTU Master or
Slave communication (NOTE: It is
Bus
imperative that the RS485-2 be powered
interfaces
by a power supply having the proper
polarity. Failure to do so will make data
transmission impossible.)
Ethernet Interfaces
communication, browser access, BACnet
IP communication, Niagara Network,
Modbus TCP)
31-00233-02
Table 3. Overview of models (hardware)
Description
e-mail
(
Max. cable
Without HMI
length
EHSERIESNX26ND
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
1200 ft
(366 m)
--
3600 ft
1)
(1097 m)
3600 ft
1)
(1097 m)
300 ft
(91.44 m)
8
Order No
With HMI
WEB-
WEB-
EHSERIESNX26D
8
2
4
4
4
1
3
26
1
1
2
8
2
4
4
4
1
3
26
1
1
2