Honeywell BC-200 Operation, Installation & Programming Manual page 100

Table of Contents

Advertisement

Appendix
9.3.2.6
P
ROGRAMMING
The LCD80 annunciator mode pre-programmed messages can be programmed in via a laptop using the BC-200
PC Interface Program. Each required message must be activated via a script in the BC-200 panel.
Switch 7 of DIP switch SW1 will enable the RS232 port on the LCD80 for programming.
The upload/download cable for the LCD-80 is a 9 pin female on one end and 3 wires on the other end.
A RS-232 serial cable is needed in the configuration as shown below:
LCD-80
1
6
7
No Connection
No Connection
Downloading new labels:
Using the PCI create an LCD-80 at the desired address.
Enter all the required descriptors in the PCI.
Set dip switch 7 to on and connect the programming cable to the LCD-80.
Select download on the PCI and tick the LCD-80 option.
The PCI will ask for the address of the LCD-80 before commencing download.
Uploading existing labels:
Using the PCI create an LCD-80 at the desired address.
Set dip switch 7 to on and connect the programming cable to the LCD-80.
Select upload on the PCI and tick the LCD-80 option.
The PCI will ask for the address of the LCD-80 before commencing upload.
BC-200 Manual – P/N DOC-01-013
EIA Name
Tx D
Signal Ground
Rx D
DTR
DSR
Note 1: Pin 4 (DTR) is connected to pin 6 (DSR) in the 9 pin connector housing.
9 PIN Connector
25 PIN Connector
3
2
5
7
2
3
4 (Note 1)
20
6 (Note 1)
6