Panel Operation
7.3.3.7.2.1 Service Menu – List – List – Analog – Modules – Status
This screen will show a reading of the selected Analog addressable module updated every 3 seconds, 255 times.
The modules current configuration is displayed together with "live readings" as shown below.
ANALOG MENU – STATUS
DAY MODE
20 JULY 2002 14:44:37
L1M1
(Z000) > BREAK GLASS ON PANEL
Poll Mode
> Flashscan Mode
Programmed As
> FMM-101-MMX-101 MINI MON
Actual Device
> FMM-101 MINI MON
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling
Device Scanned 255 Times .
PREV
NEXT
Explanations of terms:
Variable
Range
Poll Mode
CLIP
Programmed As
9 Types
Actual Device
5 Types
Device State
Normal/Active/Alarm
Device Status
23 fault types
LED Status
4 Types
BC-200 Manual – P/N DOC-01-013
A = 0
F = 0
I = 0
N = 0
TEST
RESET
Menu
Description
Shows the current polling protocol being used. CLIP = 1
module at a time. Polling mode is auto sensed at start-up
Module type programmed into panel
Module type physically seen on loop
Shows alarm or activated condition of point
Detailed description of fault condition. I.e. "No Response"
Polling, On, Off, Polling ID
Actions:
Press the PREV buttons to move to the previous
installed point.
Press the NEXT buttons to move to the next
installed point.
Press the TEST button to enter test menu for the
detector.
Press the RESET button to re-initialise the
detector.
Press MENU to return to the Analog Menu
screen.