Emergency Operation

1 E
MERGENCY
Isolate Bells
Isolate Warning System
Acknowledging an Alarm
Resetting an Alarm
Isolate an Alarm
BC-200 Manual – P/N DOC-01-013
O
PERATION
Press: EXT BELL ISOLATE
EXT BELL ISOLATE LED will light
The Bells & Buzzer will stop
A subsequent alarm will restart the Buzzer but not the bells
The bell isolate can be toggled by pressing the button a second time
Press: WARN SYS ISOLATE
WARN SYS ISOLATE LED will light
The warning system will stop
A subsequent alarm will restart the Buzzer but not the warning
system
The warning system isolate can by toggled by pressing the button a
second time
Select the Alarm using the PREV , NEXT buttons
Press: ACK to acknowledge
This will individually acknowledge alarms
Once all alarms are acknowledged the alarm LED will go steady
Select the Alarm using the PREV , NEXT buttons
Press: RESET then press ACK to confirm the resetting
This will individually acknowledge and reset alarms
Resets zone in alarm and clears all alarm inputs in the zone
If alarm is still present, the zone(s) will either stay in alarm or re-
alarm again after about 15 seconds
Select the Alarm using the PREV , NEXT buttons
Press: ISOL then press ACK to confirm the isolation
Isolates the point or zone in alarm and clears it's alarm outputs
Isolating a zone automatically acknowledges and isolates all points
in the zone