Honeywell BC-200 Operation, Installation & Programming Manual page 35

Table of Contents

Advertisement

Panel Operation
7.3.3.7.1.1 Service Menu – List – List – Analog – Detectors – Status
This screen will show a reading of the selected Analog addressable detector updated every 3 seconds, 255 times.
The detector's current configuration is displayed together with "live readings" as shown below.
Heat Detector
ANALOG MENU – STATUS
DAY MODE
20 JULY 2002 14:44:37
L1D2
(Z001) > APARTMENT 1 BATHROOM
Poll Mode
> FlashScan Mode
Programmed As
> HEAT
Actual Device
> HEAT
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling
Detector Values:
Alarm
= 0%
Temperature = 24 C
Device Scanned 255 Times .
PREV
NEXT
Note:
":Zxxx" is displayed after the descriptor, xxx is the zone number mapped to the detector. A zone number of 0
is an indication that the detector is not mapped to a zone.
Actions:
Press the PREV buttons to move to the previous installed point.
Press the NEXT buttons to move to the next installed point.
Press the TEST button to enter test menu for the detector.
Press the RESET button to re-initialise the detector.
Press MENU to return to the Analog Menu screen.
Explanations of terms:
Variable
Range
Poll Mode
CLIP
Programmed As
8 Types
Actual Device
8 Types
Device State
Normal/Active/Alarm
Device Status
23 fault types
LED Status
4 Types
Alarm
%
Pre-alarm
%
Peak Alarm Value
% or
Drift Compensation
%
Sensitivities
1-9
BC-200 Manual – P/N DOC-01-013
A = 0
F = 0
I = 0
N = 0
Peak Temperature
= 30 C
Day Alm Sensitivity= 5
Night Alarm Sens
= 1
TEST
RESET
Menu
Description
Shows the current polling protocol being used. CLIP = 1 detector
at a time. Polling mode is auto sensed at start-up
Detector type programmed into panel
Detector type physically seen on loop.
Shows alarm or activated condition of point.
Detailed description of fault condition. i.e.: "No Response"
Polling, On, Off, Polling ID
Current Percentage of alarm or Degree Celsius
Current Percentage of Pre-alarm
O
C
Highest reading since last reset.
Please refer to page 107 for information on Drift Compensation.
Detector sensitivity for day/night, alarm/pre-alarm. Please refer to
page 104 for explanation information on sensitivity settings.
Smoke Detector
ANALOG MENU – STATUS
DAY MODE
20 JULY 2002 14:44:37
L1D3
(Z990) > APARTMENT 1 BEDROOM
Poll Mode
> FlashScan Mode
Programmed As
> PHOTO-OPTICAL
Actual Device
> PHOTO-OPTICAL
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling
Detector Values:
(Needs Cleaning)
Alarm
= 0%
Peak Alarm Value
Prealarm
= 0%
Day Alm Sensitivity
Compensation = 81%
Day PreAlarm Sens
Night Alarm Sens
Night PreAlarm Sens
Device Scanned 255 Times .
PREV
NEXT
TEST
A = 0
F = 0
I = 0
N = 0
= 10%
= 5
= 5
= 1
= 1
RESET
Menu
35