Panel Operation
7.3.3.8.1.1 Service Menu – List – List – Ring – Module List – Module I/O List
Once you have selected the module, a list of all inputs and outputs for that module will be displayed in a format
specific for the module type. The example below shows the layout for an AZM-8 module which has 8 AZF inputs
and 4 programmable outputs.
MODULE I/O LIST
DAY MODE
20 JULY 2002 14:44:37
USE BUTTONS TO SELECT AN I/O:
RING 1 MODULE 1
IDENTIFIED AS AZM-8
AZF I/P
STATUS
Z01:I
Z02:IA
Z03:
Z04:F
Z05:
Z06:IF
Z07:
Z08: x
ZONE 1, KITCHEN LEVEL 6
PREV
NEXT
TEST
In the above example, the following abbreviations of STATUS apply.
Note:
If the input is a non-alarm AZF, it will display an x when the INPUT is activated.
BC-200 Manual – P/N DOC-01-013
A = 0
F = 0
I = 0
N = 0
O/P STATUS
o01:
o02: x
o03: x
o04:
CHANGE
BACK
Status
Abbreviation
A
I
F
X
Actions:
Use the PREV and NEXT buttons to scroll through
I/O points.
(The point's descriptor will display at the bottom of
the screen when each point is highlighted.)
When highlighting an AZF input point, pressing the
TEST button will take you into the test menu for
AZF's (refer page 71) providing the options for an
Alarm Test and Fault test.
When highlighting an output point, pressing the TEST
button will take you to a test menu for outputs where
you can toggle the output on/off for commissioning
test purposes. Refer to page 72.
Pressing the CHANGE button will take you to the
Modify Point Screen (refer to page 58)
Meaning
Alarm
Isolated
Fault
Activated