4 System Configuration via Web Interface

The PRO3200 comes with Access Control Device Server Manager (ACDSM). The ACDSM is a
built-in web server, through which you can configure network and other system settings.
Notes:
• If you are using Internet Explorer Enhanced Security Configuration, you cannot access the
• The default factory-set TCP/IP address for the built-in system configuration web server is

4.1 Connecting to ACDSM for the First Time

1. Use the factory default controller IP address 192.168.0.251.
2. Set the DIP switches to S4=OFF, S3=OFF, S2=ON, S1=OFF.
3. Connect the computer to host the web server via Ethernet Port 0. Connection should be via
4. Set the host computer to the static IP address 192.168.0.250 to be able to connect to the
5. Power up the PRO3200 controller.

4.2 Login Page

1. Click the "Click Here to Login" link to display the User Name and Password fields.
2. Enter your User Name and Password.
PRO3200 (PRO32IC) Installation and Configuration Guide, Document 800-15494
ACDSM web server. All pages will display "Bad Request!" You must uninstall the Enhanced
Security option before you can access the ACDSM.
192.168.0.251
S1 must be set to OFF for the factory default. After the panel powers up, change S1 to
Note:
ON to enable the use of the default user name and password.
crossover Ethernet cable or by the regular Ethernet cables connected via the hub.
factory-default PRO3200 controller at address 192.168.0.251.

Figure 5: PRO3200 Web Server Login Screen

Default User ID is admin and the default Password is password.
Note:
PRO3200 Installation
System Configuration via Web Interface