Quick Start Wizard

The Quick Start wizard groups together all the settings you need to configure for a simple
application. You can access it either via SIMATIC PDM, or via the handheld programmer.
Note
Do not use the Quick Start wizard to modify individual parameters (perform customization for
your application only after the Quick Start has been completed).
8.4
Quick start (1.)
8.4.1

Application Type (1.1.)

8.4.2

Response Rate (1.2.)

Sets the reaction speed of the device to measurement changes in the target range.
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy; faster settings allow for more level fluctuation.
74
Options
STEEL
CONCRETE
Default: STEEL
SLOW
MED
Options
FAST
Default: FAST
View menus
Update
Silo construction
0.1 m/minute
1.0 m/minute
10.0m/minute