Directing the Easy Aimer
1. Holding the electronics enclosure firmly, loosen the Easy Aimer ball locking bolts and gently
reposition the enclosure.
2. Direct SITRANS LR260 so the horn antenna is pointed at an angle perpendicular to the
material surface, if possible. (As a guide, aim the beam at a point approximately 2/3 of the
way across the tank diameter.)
3. When the desired position is reached, retighten the 5 bolts to 15-23 Nm (11 to 17 Lbf-ft).
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD
Easy Aimer ball locking bolts
Top clamping plate (upper socket)
Bottom clamping plate (lower socket)
Customer gasket as required [recommended thickness 1.5 to 1.8 mm (0.06 to 0.07")]