Commissioning
6.2 Local commissioning
6.2.3.8
High Calibration Point (HIGH CALIB. PT.) (1.6.)
Distance from Sensor Reference to High Calibration Point: usually process full level.
(See Operation (Page 52) types for an illustration.)
Values
Related parameters
When setting the High Calibration Point value, note that echoes are ignored within Near Range
(2.2.1.12.) (Page 81)
6.2.3.9
Apply (1.7.)
In order to save the Quick Start settings, it is necessary to select Yes and apply changes.
● Press Mode to return to Measurement mode.
6.2.3.10
Requesting an Echo Profile
54
Options
Range: 0.0000 to 30.000 m
Default: 0.0 m
Near Range (2.2.1.12.) (Page 81)
YES, NO, DONE
Display shows DONE when Quick Start is suc‐
cessfully completed.
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD