Communication (5.); Device Address (5.1.); Communication Control (5.2.) - Siemens SITRANS LR260 Operating Instructions Manual

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR260:
Table of Contents

Advertisement

8.8

Communication (5.)

8.8.1

Device Address (5.1.)

Sets the device address or poll ID on a HART network. Any address other than 0 will cause the
output current to be a fixed value, and the current will not indicate the reading.
Values
To set the address via the handheld programmer:
● Press RIGHT arrow to activate PROGRAM mode and open menu level 1.
● Press DOWN arrow repeatedly to navigate to COMMUNICATION (menu item 5).
● Press RIGHT arrow to display the parameter list.
● Scroll to DEVICE ADDRESS and press RIGHT arrow to open parameter view.
● Press RIGHT arrow to open Edit mode. Key in a new value and press RIGHT arrow to
accept it.
8.8.2

Communication Control (5.2.)

Note
SITRANS LR260 can only reset this parameter via the handheld programmer.
Enables /disables the read/write access to parameters via remote communications.
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD
Range: 0 to 15
Default: 0
*
Options
Read Only
No changes are permitted via remote commu‐
nications.
Read Write
Changes are permitted.
Restricted
Sets the status to Read Only, with the potential
for another HART device to change this via re‐
mote communications.
Parameter reference
8.8 Communication (5.)
111