Application Type (1.1.); Response Rate (1.2.); Units (1.3.); Operation (1.4.) - Siemens SITRANS LR260 Operating Instructions Manual

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR260:
Table of Contents

Advertisement

Commissioning
6.2 Local commissioning
6.2.3.3

Application Type (1.1.)

6.2.3.4

Response Rate (1.2.)

Sets the reaction speed of the device to measurement changes in the target range.
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy; faster settings allow for more level fluctuation.
6.2.3.5

Units (1.3.)

Select the units for the Quick Start variables (high and low calibration point, and level, distance,
or space).
Options
6.2.3.6

Operation (1.4.)

52
Options
STEEL
CONCRETE
Default: STEEL
SLOW
MED
Options
FAST
Default: FAST
NO SERVICE
LEVEL
Options
SPACE
DISTANCE
Default: DISTANCE
Silo construction
0.1 m/minute
1.0 m/minute
10.0m/minute
M, CM, MM, FT, IN
Default: M
Stops updating measurements
and associated loop current.
Last valid measurement value is
displayed.
Distance to material surface ref‐
erenced from Low Calibration
Point (process empty level).
Distance to material surface ref‐
erenced from High Calibration
Point (process full level).
Distance to material surface ref‐
erenced from Sensor Reference
Point.
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD